H2 Multi-Function Digital Output Settings
H2-
Setting
Function
Description
Control
Mode
Pg.
V/f O
LV
P
M
11
Reset Command Active
Closed: Reset command to the drive is active.
O O O
173
12
Timer Output
Timer output, controlled by b4-01 and b4-02. Used in conjunction with the digital
input (H1-
= 18 “timer function”).
O O O
173
13
Speed Agree 2
Closed: When drive output frequency equals the frequency ref/- L4-04.
O O O
173
14
User Set Speed Agree 2
Closed: When the drive output frequency is equal to the value in L4-03 (plus or minus
L4-04).
O O O
174
15
Frequency Detection 3
Closed: When the drive output frequency is less than or equal to the value in L4-03
with the hysteresis determined by L4-04.
O O O
174
16
Frequency Detection 4
Closed: When the output frequency is greater than or equal to the value in L4-03 with
the hysteresis determined by L4-04.
O O O
175
17
Torque Detection 1 (N.C.)
Open: When the output current/torque exceeds the value set in parameter L6-02 for
more time than is set in parameter L6-03.
O O O
173
18
Torque Detection 2 (N.O.)
Closed: When the output current/torque exceeds the value set in parameter L6-05 for
more time than is set in parameter L6-06.
O O O
173
19
Torque Detection 2 (N.C.)
Open: Output current/torque exceeds the value set in parameter L6-05 for more time
than is set in parameter L6-06.
O O O
173
1A
Reverse Direction
Closed: Drive is running in the reverse direction.
O O O
175
1B
During Baseblock (N.C.)
Open: Drive is in Baseblock condition. Output is disabled.
O O O
176
1C
Motor 2 Selection
Closed: Motor 2 is selected by a digital input (H1-
= 16)
O O −
176
1E
Restart Enabled
Closed: An automatic restart is performed
O O O
176
1F
Overload Alarm oL1
Closed: oL1 is at 90% of its trip point or greater.
O O O
176
20
oH Pre alarm
Closed: Heatsink temperature exceeds the parameter L8-02 value.
O O O
176
22
Mechanical Weakening
(N.O.)
Closed: Mechanical Weakening detected.
O O O
176
30
During Torque Limit
Closed: When the torque limit has been reached.
− O −
176
37
During Frequency Output
Closed: Frequency is output
Open: Operation stopped, Baseblock, DC Injection Braking, or Initial Excitation is
being performed.
O O O
176
38
Drive Enable
Closed: Multi-function input closes (H1-
= 6A)
O O O
176
39
Watt Hour Pulse Output
Output units are determined by H2-06, outputs 200 ms pulse for each incremented
kWh count.
O O O
176
3C
LOCAL/REMOTE Status
Closed: LOCAL
Open: REMOTE
O O O
177
3D
Speed Search
Closed: Speed search is being executed.
O O O
177
3E
PID Feedback Loss Low
Closed: PID Feedback Loss Low.
PID feedback value is below the level set to
b5-13 for longer than the time set in
b5-14.
O O O
177
3F
PID Feedback Loss High
Closed: PID Feedback Loss High.
PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37. O O O
177
4A
KEB Operation
Closed: KEB is being performed.
O O O
177
4B
Short-Circuit Brake
Closed: Short-Circuit Braking is active.
− − O
177
4C
During Fast-stop
Closed: Fast-stop command is entered
O O O
177
4D
oH Pre-alarm Time Limit
Closed: oH Pre-alarm time limit is passed.
O O O
177
90 to 92 FBDs Digital Outputs 1 to 3
Reserved for FBDs digital output functions.
O O O
177
100 to 192
H2 Parameter Functions
Reversed Output Switching of
0 to 92
Reverse the output switching of the multi-function output functions. Set the last two
digits of 1
to reverse the output signal of that specific function.
Examples:
Setting “108” reverses the output of “During baseblock,” which is setting value 08.
Setting “14A” reverses the output of “During KEB operation”, which is setting “4A”.
O O O
177
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
H3: Analog Inputs
Use H3 parameters to set the multi-function analog input terminals.
H3-01
Terminal A1 Signal Level
Selection
Sets the input level for terminal A1.
0: 0 to +10 V (lower limit)
1: 0 to +10 V (no lower limit)
0, 1
0
A A A
410
177
H3-02
Terminal A1 Function
Selection
Sets the function of terminal A1.
When terminal A1 is not used or is used as a through
terminal, this parameter must be set to “F”.
0 to 31
<40>
0
A A A
434
178
H3-03
<22>
Terminal A1 Gain Setting
Sets the level of the input value selected in H3-02 when 10
V is input at terminal A1.
-999.9 to
999.9
100.0
%
A A A
411
178
H3-04
<22>
Terminal A1 Bias Setting
Sets the level of the input value selected in H3-02 when 0 V
is input at terminal A1.
-999.9 to
999.9
0.0% A A A
412
178
B.2 Parameter Table
318
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...