VZA
Fuse Type
Fuse
Fuse Ampere Rating
45P5
Non-Time Delay Class T
Fuses
600 Vac, 200 kAIR
A6T50
50
47P5
A6T60
60
4011
A6T70
70
4015
A6T80
80
n
Guarding Against Harmful Materials
When installing IP20/Open-Chassis drives, use an enclosure that prevents foreign material from entering the drive from
above or below.
n
Grounding
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of grounded
systems, contact your dealer for instructions.
u
EMC Guidelines Compliance
This drive is tested according to European standards EN61800-3 and it complies with the EMC guidelines.
n
EMC Filter Installation
The following conditions must be met to ensure continued compliance with guidelines.
Refer to EMC Filters on page
385
for EMC filter selection.
Installation Method
Verify the following installation conditions to ensure that other devices and machinery used in combination with this drive
also comply with EMC guidelines.
1.
Install an EMC noise filter to the input side specified by OYMC for compliance with European standards.
2.
Place the drive and EMC noise filter in the same enclosure.
3.
Use braided shield cable for the drive and motor wiring or run the wiring through a metal conduit.
4.
Keep wiring as short as possible. Ground the shield on both the drive side and the motor side.
A
B
D
E
C
M
U/T1
V/T2
W/T3
U
V
W
A – Drive
B – 20 m max cable length between drive and motor
C – Motor
D – Metal conduit
E – Ground wire should be as short as possible.
Figure D.2 Installation Method
5.
Ground the largest possible surface area of the shield to the metal conduit when using braided shield cable. OYMC
recommends using a cable clamp.
C
B
A
A – Braided shield cable
B – Metal panel
C – Cable clamp (conductive)
Figure D.3 Ground Area
D.2 European Standards
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
383
D
Standards Compliance
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...