Register No.
Contents
002AH
Alarm Contents1
bit 0 to bit 1
Reserved
bit 2
Run Command Input Error (EF)
bit 3
Drive Baseblock (bb)
bit 4
Overtorque Detection 1 (oL3)
bit 5
Heatsink Overheat (oH)
bit 6
Overvoltage (ov)
bit 7
Undervoltage (Uv)
bit 8
Cooling Fan Error (FAN)
bit 9
MEMOBUS/Modbus Communication Error (CE)
bit A
Option Communication Error (bUS)
bit B
Undertorque Detection 1/2 (UL3/UL4)
bit C
Motor Overheat (oH3)
bit D
PID Feedback Loss (FbL, FbH)
bit E
Reserved
bit F
Serial Communication Transmission Error (CALL)
002BH
Input Terminal Status
bit 0
Terminal S1 Closed
bit 1
Terminal S2 Closed
bit 2
Terminal S3 Closed
bit 3
Terminal S4 Closed
bit 4
Terminal S5 Closed
bit 5
Terminal S6 Closed
bit 6
Reserved
bit 7 to bit F
Reserved
002CH
Drive Status 2
bit 0
During Run
bit 1
Zero Speed
bit 2
Speed Agree
bit 3
User Speed Agree
bit 4
Frequency Detection 1
bit 5
Frequency Detection 2
bit 6
Drive Ready
bit 7
During Undervoltage
bit 8
During Baseblock
bit 9
Frequency Reference from Operator Keypad
bit A
Run Command from Operator Keypad
bit B
Over/Undertorque 1, 2
bit C
Frequency Reference Loss
bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
002DH
Output Terminal Status
bit 0
Multi-Function Contact Output (terminal MA/MB-MC)
bit 1
Multi-Function Photocoupler Output 1 (terminal P1 - PC)
bit 2
Multi-Function Photocoupler Output 2 (terminal P2 - PC)
bit 3 to bit F
Reserved
002EH
Reserved
002FH
Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 Vdc units
0032H
Torque Monitor, 1% units
0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type (V0 for V1000)
0035H
Product Code 2 [ASCII], Region Code
0036H to 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PID Input, 0.1% units, signed, 100% / max. output frequency
003AH
PID Output, 0.1% units, signed, 100% / max. output frequency
003B to 003CH
Reserved
C.10 MEMOBUS/Modbus Data Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
369
C
MEMOBUS/Modbus Communications
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...