E2-11: Motor Rated Power
This parameter sets the motor rated power in kW. During Auto-Tuning the value must entered to parameter T1-02. If Auto-
Tuning completes successfully, the value entered will automatically be saved to E2-11.
No.
Parameter Name
Setting Range
Default
E2-11
Motor Rated Power
0.00 to 650.00 kW
Depending on
o2-04
n
E2-12: Motor Iron-Core Saturation Coefficient 3
This parameter sets the motor iron saturation coefficient at 130% of the magnetic flux.
No.
Parameter Name
Setting Range
Default
E2-12
Motor Iron-Core Saturation Coefficient 3
1.30 to 5.00
1.30
u
E3: V/f Characteristics for Motor 2
These parameters set the V/f pattern used for motor 2.
Refer to Setting 16: Motor 2 Selection on page 164
for details on
switching motors.
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2. Motor 2 can not be used with OLV for PM.
No.
Parameter Name
Setting Range
Default
E3-01
Motor 2 Control Mode Selection
0 or 2
0
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 like shown in
Figure 5.41
.
No.
Parameter Name
Setting Range
Default
E3-04
Motor 2 Max Output Frequency
40.0 to 400.0 Hz
50.0 Hz
E3-05
Motor 2 Max Voltage
0.0 to 255.0
<1>
200.0 V
<1>
E3-06
Motor 2 Base Frequency
0.0 to 400.0
50.0 Hz
E3-07
Motor 2 Mid Output Frequency
0.0 to 400.0
<2>
E3-08
Motor 2 Mid Output Frequency Voltage
0.0 to 255.0
<1>
<2>
E3-09
Motor 2 Minimum Output Frequency
0.0 to 400.0
<2>
E3-10
Motor 2 Minimum Output Frequency Voltage
0.0 to 255.0
<1>
<2>
E3-11
Motor 2 Mid Output Frequency 2
0.0 to 400.0
0.0 Hz
E3-12
Motor 2 Mid Output Frequency Voltage 2
0.0 to 255.0
<1>
0.0 Vac
E3-13
Motor 2 Base Voltage
0.0 to 255.0
<1>
0.0 Vac
<1> Values shown here are for 200 V class drives. Multiply voltage values by 1.15 for U-spec drives. Double the value when using a 400 V class
drive.
<2> Default setting is determined by the control mode for motor 2.
5.5 E: Motor Parameters
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
149
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...