00D8H
Option Card Fault Contents
bit 0
Option Compatibility Error (oFA00)
bit 1
Option not properly connected (oFA01)
bit 3
Option Self-diagnostics Error (oFA03)
bit 4
Option Flash Write Mode Error (oFA04)
bit 5 to F
Reserved
00FBH
Output current,
<2>
<1> Units are determined by parameter o1-03.
<2> 0.01 A units for drives set to 11 kW in Heavy or Normal Duty and 0.1 A units for drives set to 15 kW and above.
<3> The contents of a communication error are saved until the fault is reset.
<4> Depending on the motor used the correct motor pole number must be set to parameter E2-04, E4-04 or E5-05.
<5> For drive software version 1011 and later.
u
Broadcast Messages
Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not
respond.
Register No.
Contents
0001H
Digital Input Command
bit 0
Forward Run (0: Stop 1: Run)
bit 1
Direction Command (0: Forward, 1: Reverse)
bit 2, 3
Reserved
bit 4
External Fault (set by H1-01)
bit 5
Fault Reset (set by H1-02)
bit 6 to B
Reserved
bit C
Multi-Function Digital Input S5
bit D
Multi-Function Digital Input S6
bit E
Reserved
bit F
Reserved
0002H
Frequency Reference
30000/100%
u
Fault Trace Contents
The table below shows the fault codes that can be read out by MEMOBUS/Modbus commands from the U2-
monitor
parameters.
Table C.4 Fault Trace / History Register Contents
Fault Code
Fault Name
Fault Code
Fault Name
0001H
Undervoltage (Uv1)
002BH
High Slip Braking Overload (oL7)
0002H
Control Power Supply Undervoltage (Uv2)
0030H
Hardware Fault (including oFx)
0004H
Soft Charge Circuit Fault (Uv3)
0036H
Output Current Imbalance (LF2)
0006H
Ground Fault (GF)
0037H
Pullout Detection (Sto)
0007H
Overcurrent (oC)
0038H
PG Disconnected (PGo)
0008H
Overvoltage (ov)
003BH
Too many speed search restarts (SEr)
0009H
Heatsink Overheat (oH)
0041H
PID Feedback Loss (FbH)
000AH
Heatsink Overheat (oH1)
0042H
External Fault 1, input terminal S1 (EF1)
000BH
Motor Overload (oL1)
0043H
External Fault 2, input terminal S2 (EF2)
000CH
Drive Overload (oL2)
0044H
Mechanical Weakening Detection 1 (oL5)
000DH
Overtorque Detection 1 (oL3)
0045H
Mechanical Weakening Detection 2 (UL5)
000EH
Overtorque Detection 2 (oL4)
0046H
Current Offset Fault (CoF)
000FH
Dynamic Braking Transistor (rr)
0049H
FDBs fault (dWFL)
0010H
Braking Resistor Overheat (rH)
0083H
A/D Conversion Error (CPF02)
0011H
External Fault at input terminal S3 (EF3)
0084H
PWM Data Fault (CPF03)
0012H
External Fault at input terminal S4 (EF4)
0087H
Drive specification mismatch during Terminal Board or
Control Board replacement (CPF06)
0013H
External Fault at input terminal S5 (EF5)
0088H
Terminal Board Communication Fault (CPF07)
0014H
External Fault at input terminal S6 (EF6)
0089H
EEPROM Serial Communication Fault (CPF08)
0015H
Reserved
008CH
RAM fault (CPF11)
0018H
Overspeed (oS)
008DH
Flash memory circuit exception (CPF12)
0019H
Excessive Speed Deviation (dEv)
008EH
Watchdog circuit exception (CPF13)
001AH
PG Disconnect (PGo)
008FH
Control Circuit Fault (CPF14)
001BH
Input Phase Loss (PF)
0091H
Clock Fault (CPF16)
001CH
Output Phase Loss (LF)
0092H
Timing Fault (CPF17)
C.10 MEMOBUS/Modbus Data Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
373
C
MEMOBUS/Modbus Communications
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...