The following figure explains the working principle of feedback loss detection when the feedback signal is too low.
Feedback high detection works in the same way.
PID feedback value
PID
Feedback
Detection
Loss Level
(b5-13)
PID Feedback
Loss Detection Time
(b5-14)
no FbL
detection
FbL detection
time
PID Feedback
Loss Detection Time
(b5-14)
Figure 5.20 PID Feedback Loss Detection
The parameters necessary to set up the feedback loss detection are explained below.
n
b5-12: PID Feedback Loss Detection Selection
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No.
Parameter Name
Setting Range
Default
b5-12
PID Feedback Loss Detection Selection
0 to 5
0
Setting 0: Digital Output Only
A digital output set for “PID feedback low” (H2-
= 3E) will be triggered if the PID feedback value is below the
detection level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PID feedback high” (H2-
=
3F) will be triggered if the PID feedback value is beyond the detection level set to b5-36 for the time set to b5-37 or longer.
Neither a fault nor an alarm is displayed on the digital operator. The drive will continue operation. When the feedback
value leaves the loss detection range, the output is reset.
Setting 1: Feedback Loss Alarm
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low”
alarm will be displayed and a digital output set for “PID feedback low” (H2-
= 3E) will be triggered. If the PID
feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will
be displayed and a digital output set for “PID feedback high” (H2-
= 3F) will be triggered. Both events trigger an
alarm output (H1-
= 10). The drive will continue operation. When the feedback value leaves the loss detection range,
the alarm and outputs are reset.
Setting 2: Feedback Loss Fault
If the PID feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low”
fault will be displayed. If the PID feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a
“FBH - Feedback High” fault will be displayed. Both events trigger a fault output (H1-
= E) and cause the drive to
stop the motor.
Setting 3: Digital Output Only, Even if PID is Disabled by Digital Input
Same as b5-12 = 0. Detection is still active even if PID is disabled by a digital input (H1-
= 19).
Setting 4: Feedback Loss Alarm, Even if PID is Disabled by Digital Input
Same as b5-12 = 1. Detection is still active even if PID is disabled by a digital input (H1-
= 19).
Setting 5: Feedback Loss Fault, Even if PID is Disabled by Digital Input
Same as b5-12 = 2. Detection is still active even if PID is disabled by a digital input (H1-
= 19).
n
b5-13: PID Feedback Low Detection Level
Sets the feedback level used for PID feedback low detection. The PID feedback has to fall below this level for longer than
the time b5-14 before feedback loss is detected.
No.
Name
Setting Range
Default
b5-13
PID Feedback Low Detection Level
0 to 100%
0%
n
b5-14: PID Feedback Low Detection Time
Sets the time that the PID feedback has to fall below b5-13 before feedback loss is detected.
5.2 b: Application
120
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...