Status
Description
Open
Drive is not in a baseblock state.
Closed
Baseblock is being executed.
Setting 9: Frequency Reference Source
A digital output programmed for this function shows the frequency reference source that is currently selected.
Status
Description
Open
Frequency reference is provided from External Reference 1 (b1-01) or 2 (b1-15)
Closed
Frequency reference is being sourced from the digital operator.
Setting A: Run Command Source
A digital output programmed for this function shows the Run command source that is currently selected.
Status
Description
Open
Run command is provided from External Reference 1 (b1-02) or 2 (b1-16)
Closed
Run command is being sourced from the digital operator.
Setting B/17/18/19: Torque Detection 1 (N.O./N.C.) and Torque Detection 2 (N.O./N.C.)
These digital output functions can be used to signal an overtorque or undertorque situation to an external device.
Set up the torque detection and select the output function from the table below.
Refer to L6: Torque Detection on page
200
for details.
Setting
Status
Description
B
Closed
Torque Detection 1 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
17
Open
Torque Detection 1 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-02 for longer than the time specified in parameter L6-03.
18
Closed
Torque Detection 2 (N.O.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
19
Open
Torque Detection 2 (N.C.):
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in
parameter L6-05 for longer than the time specified in parameter L6-06.
Setting C: Frequency Reference Loss
An output set for this function will be closed if frequency reference loss is detected.
Refer to L4-05: Frequency Reference
Loss Detection Selection on page 197
for details.
Setting D: Dynamic Braking Resistor Overheat
An output programmed for this function will close when the dynamic braking resistor (DB) overheats or the braking
transistor is in a fault condition.
Setting E: Fault
The Fault configured digital output will close whenever the drive experiences a fault (this excludes faults CPF00 and
CPF01).
Setting F: Not Used
Use this setting when the terminal is not used or when using the terminal as a throughput.
When set to “F”, the output is not set by any drive function but it can be switched by a PLC via a communication option
or MEMOBUS/Modbus communications (through mode).
Setting 10: Minor Fault
Output closes when a minor fault condition is present.
Setting 11: Reset Command Active
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Timer Output
This setting configures a digital output terminal as output for the timer function.
Refer to b4: Delay Timers on page 115
for details.
Setting 13: Speed Agree 2 (f
ref
/f
out
Agree 2)
Closes whenever the actual output frequency is within the Speed Agree Width (L4-04) of the current frequency reference
regardless of the direction.
5.7 H: Terminal Functions
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
173
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...