F6-41: CompoNet Communication Speed
Sets the communication speed for a CompoNet option card.
No.
Parameter Name
Setting Range
Default
F6-41
CompoNet Communication Speed
0 to 255
0
Settings:
F6-41
Communication Speed
F6-41
Communication Speed
0
93.75 kbps
3
3 Mbps
1
Reserved
4
4 Mbps
2
1.5 Mbps
5 - 255
Reserved
n
F6-50: DeviceNet MAC Address
Sets the MAC address for a DeviceNet option card.
No.
Parameter Name
Setting Range
Default
F6-50
<1>
DeviceNet MAC Address
0 to 63
0
<1> Valid from drive software version 1011 and later. Parameter number was F6-20 in older software.
n
F6-51: DeviceNet Communication Speed
Sets the communication speed for a DeviceNet option card.
No.
Parameter Name
Setting Range
Default
F6-51
<1>
DeviceNet Communication Speed
0 to 4
3
<1> Valid from drive software version 1011 and later. Parameter number was F6-21 in older software
Settings:
F6-51
Communication Speed
F6-51
Communication Speed
0
125 kbps
3
Adjustable from Network
1
250 kbps
4
Auto detection
2
500 kbps
n
F6-52: DeviceNet PCA Setting
Defines the data format for data the drive receives from the DeviceNet master.
No.
Parameter Name
Setting Range
Default
F6-52
<1>
DeviceNet PCA Setting
0 to 255
0
<1> Valid from drive software version 1011 and later. Parameter number was F6-22 in older software.
n
F6-53: DeviceNet PPA Setting
Defines the data format for data sent from the drive to the DeviceNet master.
No.
Parameter Name
Setting Range
Default
F6-53
<1>
DeviceNet PPA Setting
0 to 255
0
<1> Valid from drive software version 1011 and later. Parameter number was F6-23 in older software.
n
F6-54: DeviceNet Idle Mode Fault Detection
Determines if the drive detects an EF0 fault, e.g. when no data are receive from the master (e.g., when the master is in idle
mode).
No.
Parameter Name
Setting Range
Default
F6-54
<1>
DeviceNet Idle Mode Fault Detection
0 or 1
0
<1> Valid from drive software version 1011 and later. Parameter number was F6-24 in older software.
Setting 0: Disabled, No Fault Detection
Setting 1: Enabled
n
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH - AC/DC Drive Object.
No.
Parameter Name
Setting Range
Default
F6-56
<1>
DeviceNet Speed Scaling
-15 to 15
0
F6-57
<1>
DeviceNet Current Scaling
-15 to 15
0
5.6 F: Option Settings
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
157
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...