5.8 L: Protection Functions
u
L1: Motor Protection Functions
n
L1-01: Motor Overload Protection Function Selection
The drive has an electronic overload protection function that estimates the motor overload level based on output current,
output frequency, thermal motor characteristics, and time. An oL1 fault will be triggered when motor overload is detected.
L1-01 sets the overload protection function characteristics according to the motor being used.
No.
Name
Setting Range
Default
L1-01
Motor Overload Protection Selection
0 to 4
A1-02 dependent
Note:
When the motor protection function is enabled (L1-01 is not set to zero), an oL1 alarm can be output through one of the multi-function
outputs by setting H2-01 to 1F. The output will close when the motor overload level reaches 90% of the oL1 detection level.
Setting 0: Disabled - Motor Overload Protection is not Provided
This setting should be used if no motor overheat protection is desired or if multiple motors are connected to one drive. In
this case it is recommended that you install a thermal relay for each motor as show in
Figure 5.73
Drive
Power
supply
M1
MC1
MC1, MC2: Magnetic contactors
L10, L20: Thermal relays
L10
MC2
L20
M2
Figure 5.73 Example of Protection Circuit Design for Multiple Motors
NOTICE: Protect each motor with individual thermal overloads when multiple motors are connected to one drive. Failure to comply
could result in motor damage. Disable the electronic overload protection of the drive (L1-01 = “0: Disabled”) and protect each motor
with individual motor thermal overloads.
Setting 1: General Purpose Motor (standard self-cooled)
Because the motor is self-cooled, the overload tolerance drops when the motor speed is lowered. The drive appropriately
adjusts the electrothermal trigger point according to the motor overload characteristics, protecting the motor from overheat
throughout the entire speed range.
Overload Tolerance
Overload Characteristics
Cooling Ability
Motor designed to operate from line
power.
Motor cooling is most effective when
running at rated nameplate base
frequency (check the motor
specifications).
Continuous operation at less than line
power frequency with 100% load can
trigger motor overload protection
(oL1). A fault is output and the motor
will coast to stop.
Setting 2: Drive Dedicated Motor (constant torque, 1:10)
Use this setting when operating a drive duty motor with a torque ratio of 1:10. This motor type is allowed to run with 100%
load from 10% up to 100% speed. Running slower speeds with full load can trigger an overload fault.
5.8 L: Protection Functions
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
185
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...