K is a coefficient determined by the value of C6-03:
• 10.0 kHz > C6-03 ≥ to 5.0 kHz: K = 2
• 5.0 kHz > C6-03: K = 1
• C6-03 ≥ 10.0 kHz: K = 3
Note: 1.
A carrier frequency error (oPE11) will occur when the carrier frequency proportional gain is greater than 6 while C6-03 is less than
C6-04.
2.
When C6-05 is set lower than 7, C6-04 is disabled and the carrier frequency will be fixed to the value set in C6-03.
n
Rated Current Depending on Carrier Frequency
The tables below show the drive output current depending on the carrier frequency settings. The 2 kHz value is equal to
the Normal Duty rated current, the 8/10 kHz value is equal to the Heavy Duty rated current. The carrier frequency
determines the output current linearly. Use the data below to calculate output current values for carrier frequencies not
listed in the tables.
Note:
In Heavy Duty mode the maximum rated output current is equal to the 8/10 kHz value, even if the carrier frequency is reduced.
Table 5.12 Drives with Heavy Duty Default Carrier Frequency of 10 kHz
200 V Single Phase Units
200 V Three Phase Units
Model VZA
Rated Current [A]
Model VZA
Rated Current [A]
2 kHz
10 kHz
15 kHz
2 kHz
10 kHz
15 kHz
B0P1
1.2
0.8
0.6
20P1
1.2
0.8
0.6
B0P2
1.9
1.6
1.3
20P2
1.9
1.6
1.3
B0P4
3.5
3.0
2.4
20P4
3.5
3.0
2.4
B0P7
6.0
5.0
4.0
20P7
6.0
5.0
4.0
Table 5.13 Drives with Heavy Duty Default Carrier Frequency of 8 kHz
200 V Single Phase Units
200 V Three Phase Units
400 V Three Phase Units
Model
VZA
Rated Current [A]
Model
VZA
Rated Current [A]
Model
VZA
Rated Current [A]
2 kHz
8 kHz
15 kHz
2 kHz
8 kHz
15 kHz
2 kHz
8 kHz
15 kHz
B1P5
9.6
8.0
6.4
—
—
—
—
40P2
1.2
1.2
0.7
B2P2
12.0
11.0
8.8
21P5
9.6
8.0
6.4
40P4
2.1
1.8
1.1
B4P0
17.5
17.5
14.0
22P2
12.0
11.0
8.8
40P7
4.1
3.4
2.0
—
—
—
—
—
—
—
—
41P5
5.4
4.8
2.9
—
—
—
—
24P0
19.6
17.5
14.0
42P2
6.9
5.5
3.3
—
—
—
—
25P5
30.0
25.0
20.0
43P0
8.8
7.2
4.3
—
—
—
—
27P5
40.0
33.0
26.4
44P0
11.1
9.2
5.5
—
—
—
—
2011
56.0
47.0
37.6
45P5
17.5
14.8
8.9
—
—
—
—
2015
69.0
60.0
48.0
47P5
23.0
18.0
10.8
—
—
—
—
—
—
—
—
4011
31.0
24.0
14.4
—
—
—
—
—
—
—
—
4015
38.0
31.0
18.6
5.3 C: Tuning
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
133
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...