L6-08
Mechanical Weakening
(oL5) Detection Operation
This function can detect an over/undertorque in a certain
speed range as a result of machine fatigue. It is triggered by
a certain operation time and uses the oL1 detection settings
(L6-01 to L6-02)
0: Mechanical Weakening Detection disabled.
1: Continue running (alarm only). Detected when the speed
(signed) is greater than L6-09.
2: Continue running (alarm only). Detected when the speed
(not signed) is greater than L6-09.
3: Interrupt drive output (fault). Detected when the speed
(signed) is greater than L6-09.
4: Interrupt drive output (fault). Detected when the speed (not
signed) is greater than L6-09.
5: Continue running (alarm only). Detected when the speed
(signed) is less than L6-09.
6: Continue running (alarm only). Detected when the speed
(not signed) is less than L6-09.
7: Interrupt drive output (fault). Detected when the speed
(signed) is less than L6-09.
8: Interrupt drive output (fault). Detected when the speed (not
signed) is less than L6-09.
0 to 8
0
A A A
468
201
L6-09
Mechanical Weakening
Detection Speed Level
Sets the speed that triggers mechanical weakening detection.
When L6-08 is set for an unsigned value, the absolute value
is used even if the setting is negative.
-110.0 to
+110.0% 110% A A A
469
202
L6-10
Mechanical Weakening
Detection Time
Sets the time a mechanical weakening has to be detected
before an Alarm/Fault is triggered.
0.0 to 10.0
s
0.1 s A A A
46A
202
L6-11
Mechanical Weakening
Detection Start Time
Sets the operation time (U1-04) that has to be passed before
Mechanical weakening detection is active.
0 to 65535
0
A A A
46B
202
L7: Torque Limit
Use L7 parameters to configure the torque limit function.
L7-01
Forward Torque Limit
Sets the torque limit value as a percentage of the motor rated
torque. Four individual quadrants can be set.
L7-01
L7-03
L7-02
L7-04
output torque
positive torque
REV
negative torque
FWD
motor
r/min
regeneration
regeneration
0 to 300 200% − A −
4A7
202
L7-02
Reverse Torque Limit
0 to 300 200% − A −
4A8
202
L7-03
Forward Regenerative
Torque Limit
0 to 300 200% − A −
4A9
202
L7-04
Reverse Regenerative
Torque Limit
0 to 300 200% − A −
4AA
202
L7-06
Torque Limit Integral Time
Constant
Sets the integral time constant for the torque limit.
5 to 10000 200
ms
− A −
4AC
202
L7-07
Torque Limit Control
Method Selection during
Accel/Decel
Selects the method of torque limit control during accel/decel.
0: Proportional Control (change to integral controls at fixed
speeds). Use this setting when acceleration to the desired
speed has priority over torque limitation.
1: Integral Control. Use this setting if the torque limitation
has priority.
When torque limit is applied to the motor, accel/decel time
may increase and motor speed may not meet the speed
reference.
0, 1
0
− A −
4C9
203
L8: Hardware Protection
Use L8 parameters to configure hardware protection functions.
L8-01
Internal Dynamic Braking
Resistor Protection Selection
(ERF type)
Selects the Braking resistor when using a 3% duty cycle
heatsink mounted braking resistor. This parameter does not
enable or disable the braking transistor of the drive.
0: Resistor overheat protection disabled
1: Resistor overheat protection enabled
0,1
0
A A A
4AD
203
L8-02 Overheat Alarm Level
When the heatsink temperature exceeds the value set in this
parameter, an Overheat Alarm (oH) will occur.
50 to 130
<12>
A A A
4AE
203
L8-03
Overheat Pre-Alarm
Operation Selection
Sets the drive operation when an overheat alarm oH is
detected.
0: Ramp to Stop using the active decel time.
1: Coast to Stop.
2: Fast-stop using the time set in C1-09.
3: Alarm Only. Drive continues running, but displays an
alarm.
4: Reduced Speed Operation. Drive continues to run with
reduced frequency reference as specified in L8-19.
Settings 0 through 2 trigger a fault relay if the heatsink
becomes too hot.
0 to 4
3
A A A
4AF
203
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
325
B
Parameter List
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...