C.5 MEMOBUS/Modbus Setup Parameters
u
MEMOBUS/Modbus Serial Communication
This section describes parameters necessary to set up MEMOBUS/Modbus communications.
n
H5-01: Drive Slave Address
Sets the drive slave address used for MEMOBUS/Modbus communications.
Note:
After changing this parameter, the power must be cycled to enable the new setting.
No.
Name
Setting Range
Default
H5-01
Drive Slave Address
0 to 20 H
<1>
1F
<1> If the address is set to 0, no response will be provided during communications.
For serial communications to work, each individual slave drive must be assigned a unique slave address. Setting H5-01
to any value besides 0 assigns the drive its address in the network. Slave address don't need to be assigned in sequential
order, but each address needs to be unique so that no two drives have the same address.
n
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note:
After changing this parameter, the power must be cycled to enable the new setting.
No.
Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 5
3
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
5
38400 bps
1
2400 bps
6
57600 bps
2
4800 bps
7
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
n
H5-03: Communication Parity Selection
Sets the parity used for MEMOBUS/Modbus communications.
Note:
After changing this parameter, the power must be cycled to enable the new setting.
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
Setting 0: No Parity
Setting 1: Even Parity
Setting 2: Odd Parity
n
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
No.
Name
Setting Range
Default
H5-04
Stopping Method after Communication Error
0 to 3
3
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
H5-05: Communication Fault Detection Selection
Enables or disabled the communication error (CE) detection for MEMOBUS/Modbus communications.
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
C.5 MEMOBUS/Modbus Setup Parameters
358
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...