No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
b5-06
<22>
PID Output Limit
Sets the maximum output possible from the entire PID
controller.
0.0 to
100.0
100.0
%
A A A
1AA
119
b5-07
<22>
PID Offset Adjustment
Applies an offset to the PID controller output.
-100.0 to
+100.0
0.0% A A A
1AB
119
b5-08
<22>
PID Primary Delay Time
Constant
Sets the amount of time for the filter on the output of the PID
controller.
0.00 to
10.00
0.00 s A A A
1AC
119
b5-09
PID Output Level Selection
Sets the PID controller output direction.
0: Normal Output (direct acting)
1: Reverse Output (reverse acting)
0,1
0
A A A
1AD
119
b5-10
PID Output Gain Setting
Sets the gain applied to the PID output.
0.00 to
25.00
1.00 A A A
1AE
119
b5-11
PID Output Reverse
Selection
Sets the drive operation with negative PID output.
0: Drive stops with negative PID output
1: Rotation direction reverses with negative PID output.
When using setting 1 make sure, reverse operation is
permitted by parameter b1-04.
0,1
0
A A A
1AF
119
b5-12
PID Feedback Reference
Missing Detection Selection
Configures the PID feedback loss detection. With all setting
a digital output programmed for H2-01/02/03 = 3E/3F (PID
feedback low/PID feedback high) is operated when the
detection condition becomes true.
0: Digital output only.
1: Feedback loss detected when PID enabled. Alarm output,
operation is continued without triggering a fault contact.
2: Feedback loss detected when PID enabled. Fault output,
operation is stopped and a fault contact is triggered.
3: Feedback loss detection even when PID is disabled by
digital input. No alarm/fault output.
4: PID Feedback error detection even when PID is disabled
by digital input. An alarm is triggered and the drive continues
to run.
5: PID Feedback error detection even when PID is disabled
by digital input. Fault is triggered and output is shut off.
0 to 5
0
A A A
1B0
120
b5-13
PID Feedback Loss
Detection Level
Sets the PID feedback loss detection level.
0 to 100
0%
A A A
1B1
120
b5-14
PID Feedback Loss
Detection Time
Sets the PID feedback loss detection delay time in terms of
seconds.
0.0 to 25.5 1.0 s A A A
1B2
120
b5-15
PID Sleep Function Start
Level
Sets the sleep function start frequency.
Note:
Also enabled when PID is not active.
0.0 to
400.0
0.0
Hz
A A A
1B3
121
b5-16
PID Sleep Delay Time
Sets the sleep function delay time.
0.0 to 25.5 0.0 s A A A
1B4
121
b5-17
PID Accel/Decel Time
Applies an accel/decel time to the PID setpoint.
0 to 255
0 s
A A A
1B5
121
b5-18
PID Setpoint Selection
Selects b5-19 as PID setpoint value.
0: Disabled
1: Enabled, b5-19 becomes PID target
0,1
0
A A A
1DC
122
b5-19
PID Setpoint Value
Sets the PID target value when b5-18 = 1.
0.00 to
100.00
0.00
%
A A A
1DD
122
b5-20
PID Setpoint Scaling
Sets the units for b5-19, and for parameter monitors U5-01
(PID Feedback) and U5-04 (PID Setpoint).
0: 0.01Hz units
1: 0.01% units (100% = max output frequency)
2: r/min (number of motor poles must be set up)
3: User-set (set to b5-38 and b5-39)
0 to 3
1
A A A
1E2
122
b5-34
<22>
PID Output Lower Limit
Sets the minimum output possible from the PID controller.
-100.0 to
+100.0
0.00
%
A A A
19F
122
b5-35
<22>
PID Input Limit
Limits the PID control input (deviation signal). Acts as a
bipolar limit.
0 to
1000.0
1000.
0%
A A A
1A0
122
b5-36
PID Feedback High
Detection Level
Sets the PID feedback high detection level.
0 to 100 100% A A A
1A1
121
b5-37
PID Feedback High Level
Detection Time
Sets the PID feedback high level detection delay time.
0.0 to 25.5 1.0 s A A A
1A2
121
b5-38
PID Setpoint / User Display
Sets the display value of U5-01 and U5-04 when the
maximum frequency is output. Changeable only if b5-20 = 3.
0 to 60000: User-Set Display if b5-20 = 3
1 to 60000
<5>
A A A
1FE
122
b5-39
PID Setpoint Display Digits
Sets the number of digits of U5-01 and U5-04. Changeable
only if b5-20 = 3.
0: No decimal places
1: One decimal places
2: Two decimal places
3: Three decimal places
0 to 3
<5>
A A A
1FF
122
b6: Dwell Function
Use b6 parameters to configure dwell function operation.
B.2 Parameter Table
302
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...