F6 and F7: Serial Communications Option Card Settings
These parameters are to configure communication option cards and communication fault detection methods.
n
F6-01: Communications Error Option Selection
Determines drive operation if a communication error occurs.
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error operation Selection
0 to 3
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Selection
0 or 1
0
Setting 0: Always Detected
Setting 1: Detection During Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation Selection
0 to 3
1
Setting 0: Ramp to Stop Using Current Accel/Decel Time
Setting 1: Coast to Stop
Setting 2: Fast-stop Using C1-09
Setting 3: Alarm Only, Continue Operation
n
F6-04: BUS Error Detection Time
Sets the delay time for a “bUS” error detection.
No.
Parameter Name
Setting Range
Default
F6-04
Bus Error Detection Time
0.0 to 5.0 s
2.0 s
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No.
Parameter Name
Setting Range
Default
F6-10
CC-Link Node Address
0 to 63
0
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No.
Parameter Name
Setting Range
Default
F6-11
CC-Link Communication Speed
0 to 4
0
Settings:
F6-11
Communication Speed
F6-11
Communication Speed
0
156 kbps
3
5 Mbps
1
625 kbps
4
10 Mbps
5.6 F: Option Settings
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
155
5
Parameter Details
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...