6.6 Operator Programming Errors
An Operator Programming Error (oPE) occurs when an inappropriate parameter is set or an individual parameter setting
is inappropriate.
The drive will not operate until the parameter is set correctly; however, no alarm or fault outputs will occur. If an oPE
occurs, investigate the cause and
Refer to oPE Codes, Causes, and Possible Solutions on page 247
for the appropriate
action. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant). This monitor
displays the parameter causing the oPE error.
u
oPE Codes, Causes, and Possible Solutions
Table 6.11 oPE Codes, Causes, and Possible Solutions
LED Operator Display
Error Name
oPE01
Drive Capacity Setting Fault
Drive capacity and the value set to o2-04 do not match.
Cause
Possible Solutions
The drive capacity setting (o2-04) and the actual capacity of the drive are
not the same.
Correct the value set to o2-04.
LED Operator Display
Error Name
oPE02
Parameter Range Setting Error
Use U1-18 to find parameters set outside the range.
Cause
Possible Solutions
Parameters were set outside the possible setting range.
Set parameters to the proper values.
Note:
Other errors are given precedence over oPE02 when multiple errors occur at the same time.
LED Operator Display
Error Name
oPE03
Multi-Function Input Selection Error
A contradictory setting is assigned to multi-function contact inputs H1-01
to H1-06.
Cause
Possible Solutions
• The same function is assigned to two multi-function inputs.
• Excludes “Not used” and “External Fault.”
• Ensure all multi-function inputs are assigned to different functions.
• Re-enter the multi-function settings to ensure this does not occur.
The Up command was set but the Down command was not, or vice versa
(settings 10 vs. 11).
Correctly set functions that need to be enabled in combination with other
functions.
The Up 2 command was set but the Down 2 command was not, or vice
versa (settings 75 vs. 76).
• Run/Stop command for a 2-Wire sequence was set (H1-
= 42), but
forward/reverse command (H1-
= 43) was not.
• “Drive Enable” is set to multi-function input S1 or S2 (H1-01 = 6A or
H1-02 = 6A).
Correctly set functions that need to be enabled in combination with other
functions.
Two of the following functions are set at the same time:
• Up/Down Command (10 vs. 11)
• Up 2/Down 2 Command (75 vs. 76)
• Hold Accel/Decel Stop (A)
• Analog Frequency Reference Sample/Hold (1E)
• Offset Frequency 1, 2, 3 Calculations (44, 45, 46)
• Check if contradictory settings have been assigned to the multi-function
input terminals at the same time.
• Correct setting errors.
The Up/Down command (10, 11) is enabled at the same time as PID control
(b5-01).
Disable control PID (b5-01 = “0”) or disable the Up/Down command.
Settings for NC and NO input for the following functions were selected at
the same time:
• External Search Command 1 and External Search Command 2 (61 vs.
62)
• Fast-Stop N.O. and Fast-Stop N.C.
(15 vs. 17)
• KEB for Momentary Power Loss and High Slip Braking
(65, 66, 7A, 7B vs. 68)
• Motor Switch Command and Accel/Decel Time 2
(16 vs. 1A)
• KEB Command 1 and KEB Command 2
(65, 66 vs. 7A, 7B)
• FWD Run Command (or REV) and FWD/REV Run Command (2-wire)
(40, 41 vs. 42, 43)
• External DB Command and Drive Enable
(60 vs. 6A)
• Motor Switch Command and Up 2/Down 2 Command
(16 vs. 75, 76)
Check for contradictory settings assigned to the multi-function input
terminals at the same time. Correct setting errors.
6.6 Operator Programming Errors
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
247
6
Troubleshooting
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...