No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
H3-09
Terminal A2 Signal Level
Selection
Sets the input signal level for terminal A2.
0: 0 to +10 V (with lower limit)
1: 0 to +10 V (no lower limit)
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
A A A
417
180
Switch between current or voltage inputs by
using DIP switch S1-2 switch on the terminal
board.
H3-10
Terminal A2 Function
Selection
Sets the function of terminal A2.
When terminal A2 is not used or is used as a through
terminal, this parameter must be set to “F”.
0 to 31
<40>
0
A A A
418
180
H3-11
<22>
Terminal A2 Gain Setting
Sets the level of the input value selected in H3-10 when 10
V (20 mA) is input at terminal A2.
-999.9 to
1000.0
100.0
%
A A A
419
180
H3-12
<22>
Terminal A2 Input Bias
Sets the level of the input value selected in H3-10 when 0 V
(0 or 4 mA) is input at terminal A2.
-999.9 to
999.9
0.0% A A A
41A
180
H3-13 Analog Input Filter Time
Constant
Sets the primary delay filter time constant for terminals A1
and A2. Used for noise filtering.
0.00 to 2.00 0.03 s A A A
41B
180
<22> Parameter can be changed during run.
<40> The availability of certain parameters depends on the control method used.
H3 Multi-Function Analog Input Settings
H3-
Setting
Function
Maximum Input Level Possible
Control
Mode
Pg.
V/f OL
V PM
0
Frequency Bias
Max output frequency (E1-04).
Same value can be set using H3-02 and H3-10.
O
O
O
181
1
Frequency Gain
10 V = 100%
O
O
O
181
2
Auxiliary Frequency Reference
(used as a
Multi-Step Speed 2)
Maximum output frequency (E1-04)
O
O
O
181
4
Output Voltage Bias
Motor rated voltage (E1-05).
O
–
−
181
7
Overtorque/Undertorque Detection Level
Open Loop Vector: Motor rated torque
V/f Control: Drive rated current
O
O
O
181
B
PID Feedback
10 V = 100%
O
O
O
181
C
PID Set Point
10 V = 100%
O
O
O
181
E
Motor Temperature (PTC input)
10 V = 100.00%
O
O
O
181
F
Not used/Through Mode
–
O
O
O
181
10
FWD Torque Limit
Motor rated torque
−
O
−
181
11
REV Torque Limit
Motor rated torque
−
O
−
181
12
Regenerative Torque Limit
Motor rated torque
−
O
−
181
15
FWD/REV Torque Limit
Motor rated torque
−
O
−
181
16
Differential PID Feedback
10 V = 100%
O
O
O
182
30/31
FBDs Analog Input 1/2
Depending on function.
O
O
O
182
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f OL
V
P
M
H4: Multi-Function Analog Outputs
Use H4 parameters to configure the multi-function analog output terminals.
H4-01
Multi-Function Analog
Output Terminal AM
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
U
-
. For example, enter “103” for U1-03.
When using this terminal in through mode or when not using
it at all, set “000” or “031”.
000 to 999
<40>
102
A A A
41D
182
H4-02
<22>
Multi-Function Analog
Output Terminal AM Gain
Sets terminal AM output gain.
Maximum output voltage is 10 V.
-999.9 to
999.9
100.0
%
S
S
S
41E
182
H4-03
<22>
Multi-Function Analog
Output Terminal AM Bias
Sets terminal AM output bias.
-999.9 to
999.9
0.0% A A A
41F
182
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
H5-01
<39>
Drive Node Address
Selects drive station node number (address) for MEMOBUS/
Modbus terminals R+, R-, S+, S-. Cycle power for the setting
to take effect.
0 to 20 H
1F
A A A
425
358
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
319
B
Parameter List
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...