B.3 Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor 1, E3-01 for motor 2). These
parameters are initialized to the shown values if the control mode is changed.
Table B.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
Parameter
Description
Setting Range
Resolution
Control Modes (A1-02)
V/f (0)
OLV (2)
PM (5)
b3-02
Speed Search deactivation current
0 to 200
1%
120
100
–
b8-02
Energy Saving gain
0.0 to 10.0
0.1
–
0.7
–
C2-01
S-curve time at acceleration start
0.00 to 10.00
0.01 s
0.20
0.20
1.00
C3-01
Slip compensation gain
0.0 to 2.5
0.1
0.0
1.0
–
C3-02
Slip compensation time constant
0 to 10000
1 ms
2000
200
–
C4-01
Torque compensation gain
0.00 to 2.50
0.01
1.00
1.00
0.00
C4-02
Torque comp. primary delay time
0 to 10000
1 ms
200
20
100
C6-02
Carrier frequency
1 to F
1
<12>
<12>
2
E1-04
Maximum output frequency
40.0 to 400.0
0.1 Hz
50.0
50.0
<10>
E1-05
Maximum output voltage
<24>
0.0 to 255.0
0.1 V
200.0
200.0
<10>
E1-07
Middle output frequency
0.0 to 400.0
0.1 Hz
2.5
3.0
–
E1-09
Minimum output frequency
0.0 to 400.0
0.1 Hz
1.3
0.5
<10>
E1-10
Minimum output voltage
<24>
0.0 to 255.0
0.1 V
12.0
3.0
–
E1-11
Middle output frequency 2
0.0 to 400.0
0.1 Hz
0.0
0.0
–
E1-12
Middle output freq. voltage 2
<24>
0.0 to 255.0
0.1 V
0.0
0.0
–
E1-13
Base voltage
<24>
0.0 to 255.0
0.1 V
0.0
0.0
–
L1-01
Motor protection selection
0 to 4
-
1
1
4
L3-20
Accel/Decel rate calculation rate
0.00 to 5.00
0.01
1.00
0.30
0.65
L3-21
Decel time at Stall Prevention during
acceleration
0.00 to 200.00
0.01
1.00
1.00
2.50
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
Parameter
Description
Setting Range
Resolution
Control Modes (E3-01)
V/f (0)
OLV (2)
E3-04
Maximum output frequency
40.0 to 400.0
0.1 Hz
50.0
50.0
E3-05
Maximum output voltage
<24>
0.0 to 255.0
0.1 V
200.0
200.0
E3-06
Base Frequency
0.0 to 400.0
0.1 Hz
50.0
50.0
E3-07
Middle output frequency
0.0 to 400.0
0.1 Hz
2.5
3.0
E3-08
Middle output freq. voltage
<24>
0.0 to 255.0
0.1 V
16.0
14.4
E3-09
Minimum output frequency
0.0 to 400.0
0.1 Hz
1.3
0.5
E3-11
Middle output frequency 2
0.0 to 400.0
0.1 Hz
0.0
0.0
E3-12
Middle output freq. voltage 2
<24>
0.0 to 255.0
0.1 V
0.0
0.0
E3-13
Base voltage
<24>
0.0 to 255.0
0.1 V
0.0
0.0
E3-14
Motor 2 Slip compensation gain
0.0 to 2.5
0.1
0.0
1.0
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
B.3 Control Mode Dependent Parameter Default Values
338
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...