![Omron V1000 Скачать руководство пользователя страница 389](http://html.mh-extra.com/html/omron/v1000/v1000_user-manual_741325389.webp)
D.3 UL Standards
The UL/cUL mark applies to products in the United States and Canada indicates that UL has performed product testing
and evaluation and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
UL
C
R
US
LISTED
Figure D.7 UL/cUL Mark
u
UL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The following conditions
must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
n
Main Circuit Terminal Wiring
OYMC recommends using UL-listed copper wires (rated at 75 °C) and closed-loop connectors or CSA-certified ring
connectors sized for the selected wire gauge to maintain proper clearances when wiring the drive. Use the correct crimp
tool to install connectors per manufacturer recommendation.
Table D.5
lists a suitable closed-loop connector manufactured
by JST Corporation.
Table D.5 Closed-Loop Crimp Terminal Size (JIS C 2805) (same for 200 V and 400 V)
Wire Gauge
mm
2
(AWG)
Terminal
Screws
Crimp Terminal
Model Numbers
Tightening Torque
N m (lb to in.)
0.75 (18)
M3.5
R1.25-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R1.25-4
1.2 to 1.5 (10.6 to 13.3)
1.25 (16)
M3.5
R1.25-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R1.25-4
1.2 to 1.5 (10.6 to 13.3)
2 (14)
M3.5
R2-3.5
0.8 to 1.0 (7.1 to 8.9)
M4
R2-4
1.2 to 1.5 (10.6 to 13.3)
M5
R2-5
2.0 to 2.5 (17.7 to 22.1)
M6
R2-6
4.0 to 5.0 (35.4 to 44.3)
3.5/5.5 (12/10)
M4
R5.5-4
1.2 to 1.5 (10.6 to 13.3)
M5
R5.5-5
2.0 to 2.5 (17.7 to 22.1)
M6
R5.5-6
4.0 to 5.0 (35.4 to 44.3)
M8
R5.5-8
9.0 to 11.0 (79.7 to 97.4)
8 (8)
M4
8-4
1.2 to 1.5 (10.6 to 13.3)
M5
R8-5
2.0 to 2.5 (17.7 to 22.1)
M6
R8-6
4.0 to 5.0 (35.4 to 44.3)
M8
R8-8
9.0 to 11.0 (79.7 to 97.4)
14 (6)
M4
14-4
<1>
1.2 to 1.5 (10.6 to 13.3)
M5
R14-5
2.0 to 2.5 (17.7 to 22.1)
M6
R14-6
4.0 to 5.0 (35.4 to 44.3)
M8
R14-8
9.0 to 11.0 (79.7 to 97.4)
22 (4)
M6
R22-6
4.0 to 5.0 (35.4 to 44.3)
M8
R22-8
9.0 to 11.0 (79.7 to 97.4)
30/38 (3/2)
M8
R38-8
9.0 to 11.0 (79.7 to 97.4)
<1> Use the specified crimp terminals (Model 14–NK4) when using VZA25P5, VZA27P5, and VZA47P5 with 14 mm
2
(6 AWG).
Note:
Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable
temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.
D.3 UL Standards
388
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...