B.2 Parameter Table
u
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
A1-01
<22>
<16>
Access Level Selection
Selects which parameters are accessible via the digital operator.
0: Operation only
1: User Parameters (access to a set of parameters selected by the
user)
2: Advanced Access Level
0 to 2
2
A A A
101H
98
A1-02 Control Method
Selection
Selects the Control Method of the drive.
0: V/f Control without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note:
Does not return to the default setting when the drive is
initialized.
0, 2, 5
0
S S S
102
98
A1-03 Initialize Parameters
Resets all parameters to factory default settings. (Initializes the
drive then returns A1-03 to 0)
0: No Initialize
1110: User Initialize
(First set user parameter values must be stored using parameter
o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
5550: oPE04 Error Reset
0 to 3330
0
A A A
103
98
The following parameters are not reset when
the performing initialization: A1-00, A1-02,
A1-07, and all U2 and U3 monitors.
A1-04 Password 1
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03, A1-06, and A2-01
through A2-32 cannot be changed.
0 to 9999
0
A A A
104
99
A1-05 Password 2
0 to 9999
0
A A A
105
99
This parameter is hidden from view. To
access A1-05, first display A1-04. Then
press the STOP key while holding down
the up arrow key. Parameter A1-05 will
appear.
—
A1-06 Application Preset
Sets parameters that are commonly used in certain applications to
A2-01 through A2-16 for easier access.
0: General-purpose (A2 parameters are not affected)
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Elevator
7: Hoist
0 to 7
0
A A A
127
82
A1-07 FBDs Function
Selection
0: Disabled
1: Enabled
2: Multi-function input (enabled when H1-
= 9F)
0 to 2
0
A A A
128
100
A2: User Parameters
Use A2 parameters to program the drive.
A2-01 to
A2-32
User Parameters, 1 to
32
Parameters that were recently edited are listed here. The user can
also select parameters to appear here for quick access. Parameters
will be stored here for quick access when A1-01 = 1.
b1-01 to
o2-08
--
<16>
A A A 106 to
125
101
A2-33 User Parameter
Automatic Selection
0: Parameters A2-01 through A2-32 are reserved for the user to
create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited
parameters will be saved to A2-17 through A2-32 for quick access.
0,1
1
<4>
A A A
126
101
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0.
<16> Default setting value is dependent on parameter A1-06, Application Selection.
<22> Parameter can be changed during run.
u
b: Application
Application parameters configure the Run Command Source, DC Injection Braking, Speed Search, Timer functions, PID
control, the Dwell function, Energy Savings and a variety of other application-related settings.
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
299
B
Parameter List
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...