No.
Parameter Name
Setting Range
Default
C3-02
Slip Compensation Primary Delay Time
0 to 10000 ms
Determined by
A1-02
Note:
When using V/f Control (A1-02 = 0), the default setting becomes 2000 ms. When using Open Loop Vector Control (A1-02 = 2), the default
setting becomes 200 ms. This function is not available when using V/f Control with Simple PG Feedback.
n
C3-03: Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E2-02).
No.
Parameter Name
Setting Range
Default
C3-03
Slip Compensation Limit
0 to 250%
200%
The slip compensation limit is constant throughout the constant torque range. In the constant power range it is increased
based on C3-03 and the output frequency as shown in the following diagram.
Note:
This parameter is disabled when using V/f Control with Simple PG Feedback Control (H6-01 = 3).
E1-04
E1-06 × C3-03
C3-03
E1-04
Maximum
Frequency
E1-06
Base
Frequency
output frequency
Figure 5.26 Slip Compensation Limit
n
C3-04: Slip Compensation Selection during Regeneration
When the slip compensation during regeneration function has been activated and regenerative load is applied, it might be
necessary to use a braking option (braking resistor, braking resistor unit, or braking unit).
Even if enabled, this function does not operate when the output frequency is too low.
No.
Parameter Name
Setting Range
Default
C3-04
Slip Compensation Selection during Regeneration
0 or 1
0
Setting 0: Disabled
Slip compensation is not provided. Depending on the load and operation mode (motoring or regenerative) the actual motor
speed will be lower or higher than the frequency reference.
Setting 1: Enabled
Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.
n
C3-05: Output Voltage Limit Operation Selection
Determines if the motor flux reference is automatically reduced when output voltage reaches the saturation range.
No.
Parameter Name
Setting Range
Default
C3-05
Output Voltage Limit Operation Selection
0 or 1
0
Setting 0: Disabled
Setting 1: Enabled
u
C4: Torque Compensation
The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.
Note:
Before making changes to the torque compensation parameters make sure the motor parameters and V/f pattern are set properly or perform
Auto-Tuning.
n
C4-01: Torque Compensation Gain
Sets the gain for the torque compensation function.
No.
Parameter Name
Setting Range
Default
C4-01
Torque Compensation Gain
0.00 to 2.50
Determined by
A1-02
5.3 C: Tuning
128
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...