T1-04: Motor Rated Current
Used to set the motor rated current according to the motor nameplate value. For optimal performance in OLV, the motor
rated current should be between 50 and 100% of the drive rating. Enter the current at the motor base speed.
No.
Name
Setting Range
Default
T1-04
Motor Rated Current
10 to 200% of drive rated
current
Determined by
o2-04 and C6-01
n
T1-05: Motor Rated Frequency (T1-01 = 0 or 3)
Used to set the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range
is used or the motor is used in the field weakening area, enter the base frequency here.
For higher tuning precision and better control performance, enter the motor no-load frequency here if known. The “no-
load frequency” refers to the frequency needed to operate the motor under no-load condition at its rated speed. Refer to
the motor data sheet.
No.
Name
Setting Range
Default
T1-05
Motor Base Frequency
0.0 to 400.0 Hz
50.0 Hz
n
T1-06: Number of Motor Poles (T1-01 = 0 or 3)
Used to set the number of motor poles according to the motor nameplate value.
No.
Name
Setting Range
Default
T1-06
Number of Motor Poles
2 to 48
4
n
T1-07: Motor Rated Speed (T1-01 = 0 or 3)
Used to set the motor rated speed according to the motor nameplate value. If a motor with an extended speed range is used
or the motor is used in the field weakening area, enter the speed at base frequency here.
No.
Name
Setting Range
Default
T1-07
Motor Base Speed
0 to 24000 r/min
1450 r/min
n
T1-11: Motor Iron Loss (T1-01 = 3)
Provides iron loss information for determining the Energy Saving coefficient. If E2-10 has been changed and the power
has been cycled, the value set to E2-10 will appear as the default in T1-11. If the value of T1-02 is not changed during
Auto-Tuning data input, the drive will select a value that is typical for the motor power entered to T1-02.
No.
Name
Setting Range
Default
T1-11
Motor Iron Loss
0 to 65535 W
Determined by
o2-04 and C6-01
4.7 Auto-Tuning
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
91
4
Start-Up Programming & Operation
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...