No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
L3-21
Accel/Decel Rate
Calculation Gain
Sets the proportional gain used to calculate the deceleration
rate during KEB, ov suppression function and Stall
Prevention during deceleration (L3-04 = 2).
This parameter does not typically require adjustment.
Increase the value in steps of 1.0 if overcurrent and
overvoltage occur.
0.00 to
200.00
1.00 A A A
466
196
L3-22
Deceleration Time at Stall
Prevention during
Acceleration
Sets the deceleration time used for Stall Prevention during
acceleration in Open Loop Vector Control for PM motors.
When set to 0, the drive decelerates at the normal deceleration
time.
0.0 to
6000.0
0.0 s − − A
4F9
193
L3-23
Automatic Reduction
Selection for Stall Prevention
during Run
0: Sets the Stall Prevention level throughout the entire
frequency range to the value in parameter L3-06.
1: Automatically lowers the Stall Prevention level in the
constant output range. The lower limit value is 40% of L3-06.
0, 1
0
A A Α
4FD
195
L3-24
Motor Acceleration Time for
Inertia Calculations
Sets the time needed to accelerate the uncoupled motor at
rated torque from stop to the maximum frequency.
Setting the drive capacity to parameter o2-04 or changing
E2-11 will automatically set this parameter for a 4-pole
motor.
0.001 to
10.000
<10>
<51>
<57>
A A A
46E
196
L3-25
Load Inertia Ratio
Sets the ratio between the motor and machine inertia.
0.0 to
1000.0
1.0
A A A
46F
197
L4: Frequency Detection
Use L4 parameters to configure frequency detection operation.
L4-01
Speed Agreement Detection
Level
These parameters configure the multi-function output (H2-
= 2, 3, 4, 5) settings "Speed Agree 1", "User Set Speed
Agree 1", "Frequency Detection 1," and "Frequency
detection 2".
Parameter L4-01 sets the level while parameter L4-02 sets
the hysteresis for the Speed Detection Output Function.
0.0 to
400.0
0.0 Hz A A A
499
197
L4-02
Speed Agreement Detection
Width
0.0 to 20.0 2.0 Hz A A A
49A
197
L4-03
Speed Agreement Detection
Level (+/-)
These parameters configure the Multi-Function Output (H2-
= 13, 14, 15, 16) settings "Speed Agree 2", "User Set
Speed Agree 2", "Frequency Detection 3," or "Frequency
Detection 4".
Parameter L4-03 sets the level while parameter L4-04 sets
the hysteresis for the Speed Detection Output Function.
-400.0 to
+400.0 0.0 Hz A A A
49B
197
L4-04
Speed Agreement Detection
Width (+/-)
0.0 to 20.0 2.0 Hz A A A
49C
197
L4-05
Frequency Reference Loss
Detection Selection
Sets operation when the frequency reference is lost (reference
drops 90% or more within 400 ms).
0: Stop - Drive will stop.
1: Run at L4-06 Level - Drive will run at the percentage set
in L4-06 of the frequency reference before loss.
0,1
0
A A A
49D
197
L4-06
Frequency Reference at
Reference Loss
Sets the frequency reference when a reference loss was
detected and L4-05 = 1. Reference will be: Fref = Fref at time
of loss x L4-06.
0.0 to
100.0
80.0% A A A
4C2
198
L4-07 Frequency Detection
Conditions
0: No detection during baseblock.
1: Detection always enabled.
0 to 1
0
A A A
470H
198
L5: Fault Reset
Use L5 parameters to configure Automatic Restart after fault.
L5-01
Number of Auto Restart
Attempts
Sets the counter for the number of times the drive attempts
to restart when one of the following faults occurs: GF, LF,
oC, ov, PF, rH, rr, oL1, oL2, oL3, oL4, Uv1.
Parameter L5-05 determines the how the restart counter is
incremented.
When the drive operates without fault for 10 minutes, the
counter will be reset.
0 to 10
0
A A A
49E
199
L5-02
Auto Restart Operation
Selection
Sets fault contact (H2-
= E) activation during automatic
restart attempts.
0: Fault output not active.
1: Fault output active during restart attempt.
0,1
0
A A A
49F
199
L5-04
Fault Reset Interval Time
Sets the amount of time to wait between performing fault
restarts. Enabled when L5-05 is set to 1.
0.5 to
600.0 s
10.0 s A A A
46C
199
L5-05
Fault Reset Operation
Selection
Selects the method of incrementing the restart counter.
0: Continuously attempt to restart and increment counter after
successful restart (same as Varispeed VS616-F7/G7)
1: Attempt to restart with the interval time set in L5-04. Every
trial increments the counter. (same as Varispeed VS606-V7)
0 to 1
0
A A A
467
199
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
323
B
Parameter List
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...