No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
C6-03
Carrier Frequency Upper
Limit
Open Loop Vector: C6-03 defines the fixed carrier
frequency if C6-02 = F.
V/f Control: C6-03 and C6-04 set upper and lower limits
for the carrier frequency.
carrier frequency
E1-04
max output
frequency
output frequency
× (C6-05) × K
output
frequency
C6-03
C6-04
The coefficient K depends on C6-03:
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
When C6-05 ≤ 6, C6-04 is disabled (makes the carrier
frequency C6-03 value).
1.0 to 15.0
<8>
A A A
225
132
C6-04
Carrier Frequency Lower
Limit
0.4 to 15.0
<8>
A
-
-
226
132
C6-05
Carrier Frequency
Proportional Gain
Sets the relationship of output frequency to carrier
frequency when C6-02 = F.
00 to 99
<8>
A
-
-
227
132
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<3> Default setting value is dependent on parameters o2-04, Drive Model Selection, A1-02, Control Method Selection and C6-01, Normal/Heavy
Duty selection.
<6> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of 0.01 seconds), the setting
range becomes 0.00 to 600.00 seconds.
<8> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
<22> Parameter can be changed during run.
<23> Parameter cannot be changed during run when parameter A1-02 = 5-PM OLV Control.
u
d: References
Reference parameters are used to set the various frequency reference values during operation.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
d1: Frequency Reference
Use d1 parameters to configure the drive frequency reference.
d1-01
<22>
Frequency Reference 1
Frequency reference
0.00 to
400.00 Hz
<11>
<19>
0.00
Hz
S S S
280
135
d1-02
<22>
Frequency Reference 2
Frequency reference when digital input "Multi-Step Speed
Reference 1" (H1-
= 3) is on.
0.00
Hz
S S S
281
135
d1-03
<22>
Frequency Reference 3
Frequency reference when digital input "Multi-Step Speed
Reference 2” (H1-
= 4) is on.
0.00
Hz
S S S
282
135
d1-04
<22>
Frequency Reference 4
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 2" (H1-
= 3 and 4) are on.
0.00
Hz
S S S
283
135
d1-05
<22>
Frequency Reference 5
Frequency reference when digital input "Multi-Step Speed
Reference 3" (H1-
= 5) is on.
0.00
Hz
A A A
284
135
d1-06
<22>
Frequency Reference 6
Frequency reference when digital inputs "Multi-Step Speed
Reference 1, 3 " (H1-
= 3 and 5) are on.
0.00
Hz
A A A
285
135
d1-07
<22>
Frequency Reference 7
Frequency reference when digital inputs "Multi-Step Speed
Reference 2, 3" (H1-
= 4 and 5) are on.
0.00
Hz
A A A
286
135
d1-08
<22>
Frequency Reference 8
Frequency reference when multi-function input "Multi-Step
speed reference 1, 2, 3" (H1-
= 3, 4, 5) are on.
0.00
Hz
A A A
287
135
d1-09
<22>
Frequency Reference 9
Frequency reference when multi-function input "Multi-Step
Speed Reference 4" (H1-
= 32) is on.
0.00
Hz
A A A
288
135
d1-10
<22>
Frequency Reference 10
Frequency reference when digital input "Multi-Step Speed
Reference 1, 4" (H1-
= 3 and 32) are on.
0.00
Hz
A A A
28B
135
B.2 Parameter Table
306
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...