Setting 4: Pulse Train Input
If b1-01 is set to 4 the frequency reference must be provided by a pulse train signal at terminal RP that complies with the
following specification.
Pulse Train Input Specifications
Response Frequency
0.5 to 32 kHz
Duty Cycle
30 to 70%
High Level Voltage
3.5 to 13.2 V
Low Level Voltage
0.0 to 0.8 V
Input Impedance
3 kΩ
Verifying Pulse Train is Working Properly
• Make sure that b1-04 is set to 4 and H6-01 is set to 0.
• Set the pulse input scaling H6-02 to the pulse train frequency value that equals 100% frequency reference.
• Enter a pulse train signal to terminal RP and check if the correct frequency reference is displayed. Try also with different
pulse train input frequencies.
n
b1-02: Run Command Selection 1
Parameter b1-02 determines the Run and Stop command source 1 in the REMOTE mode.
WARNING! Sudden Movement Hazard. Clear personnel, secure equipment, and check sequence and safety circuitry before starting
the drive. Failure to comply could result in death or serious injury from moving equipment.
No.
Parameter Name
Setting Range
Default
b1-02
Run Command Selection 1
0 to 3
1
Setting 0: Operator
Using this setting, the RUN and STOP keys on the operator keypad will start and stop the motor. The LED in the LO/RE
key will be on to indicate that the Run command is assigned to the operator. The example below shows how the drive can
be operated if b1-02 is set to 0.
Step
Display/Result
1.
Turn on the power to the drive. The initial display appears.
2.
Set the frequency reference to F6.00 (6 Hz).
3.
Press the
key to start the motor. The RUN indicator LED will light and the motor
will begin rotating at 6 Hz.
STOP
off
on
4.
Press the
key to stop the motor. The RUN light will flash until the motor comes
to a complete stop.
flashing
off
Setting 1: Control Circuit Terminal
This setting requires that the Run and Stop commands are entered from the digital input terminals. The following sequences
can be used:
• 2-Wire sequence 1:
Two inputs (FWD/Stop-REV/Stop). Initializing the drive by setting A1-01 = 2220, presets the terminals S1 and S2 to
these functions. This is the default setting of the drive.
Refer to Setting 40/41: Forward Run/Reverse Run Command
for 2-Wire Sequence on page 166
.
• 2-Wire sequence 2:
Two inputs (Start/Stop-FWD/REV).
Refer to Setting 42/43: Run and Direction Command for 2-Wire Sequence 2 on
page 166
.
• 3-Wire sequence:
Inputs S1, S2, S5 (Start-Stop-FWD/REV). Initialize the drive by setting A1-01 = 3330 presets the terminals S1, S2 and
S5 to these functions.
Refer to Setting 0: 3-Wire Sequence on page 160
.
Setting 2: MEMOBUS/Modbus Communications
To issue a Run command via serial communications, set b1-02 to “2” and connect the RS-485/422 serial communication
cable to R+, R-, S+, and S- on the removable terminal block.
Refer to MEMOBUS/Modbus Communications on page
351
.
5.2 b: Application
104
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23
Содержание V1000
Страница 11: ...Table of Contents This Page Intentionally Blank 10 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 27: ...1 4 Component Names This Page Intentionally Blank 26 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 37: ...2 2 Mechanical Installation This Page Intentionally Blank 36 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 63: ...3 12 Wiring Checklist This Page Intentionally Blank 62 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 221: ...5 11 U Monitor Parameters This Page Intentionally Blank 220 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 273: ...7 5 Drive Replacement This Page Intentionally Blank 272 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 287: ...8 6 Connecting an Option Card This Page Intentionally Blank 286 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 297: ...A 6 Drive Derating Data This Page Intentionally Blank 296 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 379: ...C 13 Self Diagnostics This Page Intentionally Blank 378 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 409: ...Index This Page Intentionally Blank 408 SIEP C710606 20 OYMC AC Drive V1000 User Manual ...
Страница 410: ...This Page Intentionally Blank SIEP C710606 20 OYMC AC Drive V1000 User Manual 409 ...