User Manual

Interface Adapter

Optical Fiber 

 RS-232

Summary of Contents for PTS DP1

Page 1: ...PTS DP1 H A R D W A R E User Manual Interface Adapter Optical Fiber RS 232 ...

Page 2: ...eserves the right to make technical changes without announcement OMICRON electronics is not to be held liable for statements and declarations given in this manual The user is responsible for every application described in this manual OMICRON electronics explicitly exonerates itself from all liability for mistakes in this manual Copying or reproducing this manual wholly or in part is not permitted ...

Page 3: ...Position Monitoring Mode 8 3 2 LIGHT ON LIGHT OFF Switch 8 3 3 OR NORM Switch 9 OR Position 9 NORM Position 9 4 Cables and Connections 10 4 1 RS 232 Interface Cable 10 4 2 Fiber Connections for ST Connectors 10 4 3 Fiber Connections for FSMA Connectors 10 5 Technical Data 11 5 1 Interfaces 11 Optical Interfaces 11 Electrical Interfaces 11 5 2 Power Supply 11 5 3 Environmental Conditions 12 Climate...

Page 4: ...the PTS DP1 under wet or moist conditions Do not operate the PTS DP1 when explosive gases or vapors are present Do not open the PTS DP1 There are no user serviceable parts inside All guarantees become void if the device is opened The PTS DP1 is a product of laser class 1 IEC 60825 1 Accessible Emission Limit AEL class 1 LED devices are considered eye safe ...

Page 5: ...rom a mains adapter 2 1 Standard Components The standard delivery is prepared for connecting to devices with ST connectors Following components are included in the standard delivery Description Article Number PTS DP1 Interface Adapter Set VEGG0030 Qty Description 1 PTS DP1 Interface Adapter unit 1 PTS DP1 User Manual 1 Power supply unit 100 240V AC VEHZ1108 1 Fiber patch cable glass fiber 62 5 125...

Page 6: ...nel 2 are located optical interface OPTICAL 2 electrical interface RS 232 2 the power connector LED Indicators Each terminal of the optical interfaces transmitter and receiver has a LED assigned indicating the light level present on the terminal There are three different conditions indicated Constant green no light Constant red light Blinking activity light level is changing The LED indicator at t...

Page 7: ...PTICAL 2 is connected to RS 232 2 Two independent bidirectional optical electrical converters are established The PC with the protocol testing software can simulate a relay to the control center or a control center to the relay Primary Station master control center Secondary Station slave relay PTS DP1 PC with PTS 103 simulating a primary station PC with PTS 103 simulating a secondary station PTS ...

Page 8: ...ng mode with one or two serial interfaces Primary Station master control center Secondary Station slave relay PTS DP1 PTS DP1 in monitoring mode The described mode of operation requires the OR NORM switch being in NORM Position 3 2 LIGHT ON LIGHT OFF Switch This selection is to adopt to the light position for idle status on the optical interface The LIGHT ON position is is the one defined in the I...

Page 9: ... the option Monitoring of halfduplex communication on the bottom of the Interfaceparameter dialog has to be checked The direction of the data is determined from the telegram type single byte acknowledge E5 is always secondary primary and the PRM bit in the control byte of the link header OR Position The data received from the two optical links are ORed Identical data are available on both RS 232 i...

Page 10: ...ns for ST Connectors This connection can be made with the patch cable included in the standard delivery PTS DP1 Primary Station master control center Secondary Station slave relay Slave device with ST sockets Originally installed cable with ST connectors ST ST patch cable 4 3 Fiber Connections for FSMA Connectors To connect to devices with FSMA connectors the FSMA connection set is provided PTS DP...

Page 11: ...type Wavelength 820nm Distances up to 500m with 50 125µm glass fiber up to 1500m with 62 5 125µm glass fiber Electrical Interfaces RS 232 1 RS 232 2 Connector D Sub 9 pin male Singal levels RS 232 Signals supported Tx Rx GND 5 2 Power Supply Power Supply Nominal voltage 18V DC DC supply voltage 8 30V AC supply voltage 10 20V Power consumption max 2W ...

Page 12: ...N 50081 2 Immunity EN 50082 2 IEC 61000 4 2 3 4 6 5 4 Safety Standards Safety Standards Safety comformity EN 61010 1 IEC 61010 1 5 5 Mechanical Data Dimensions and Mass Dimensions W x L x H 110mm x 165mm x 37mm Mass 200g 5 6 Cleaning For cleaning the PTS DP1 use a cloth damped with isopropanol alcohol or water 6 Manufacturer Contact Information OMICRON electronics GmbH Oberes Ried 1 6833 Klaus Aus...