2 Initial Settings and Allocations of Device Variable for CJ-series Unit
2-22
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
z
Modbus-RTU Slave Mode
Device variable for CJ-series Unit
Type
R/W
Name
Function
Port 1
Port 2
*_P1_MbsSlavAdrCfg
*_P2_MbsSlavAdrCfg
USINT
RW
Modbus-RTU
Slave Address
Range: 1 to 247
Default: 0
*_P1_MbsCoilsAreaCfg
*_P2_MbsCoilsAreaCfg
BYTE
RW
Coils Alloca-
tion Area
16#00: CIO (default)
16#B0: CIO
16#B1: WR
16#B2: HR
16#B3: AR
*_P1_MbsRegAreaCfg
*_P2_MbsRegAreaCfg
WORD
RW
Modbus-RTU
Settings
Bits 08 to 15 Input Regis-
ters Area allocation area
Bits 00 to 07 Holding Reg-
isters Area allocation area
*_P1_MbsInRegArea
Cfg
*_P2_MbsInRegArea
Cfg
BYTE
RW
Input Registers
Allocation Area
16#00: CIO (default)
16#B0: CIO
16#B1: WR
16#B2: HR
16#B3: AR
*_P1_MbsHdRegArea
Cfg
*_P2_MbsHdRegArea
Cfg
BYTE
RW
Holding Regis-
ters Allocation
Area
16#00: DM (default)
16#82: DM
16#50 to 5C:
EM bank 0 to bank C
16#A0 to AC:
EM bank 0 to bank C
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...