3 Installation and Wiring
3-10
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Note 1
The maximum cable length for RS-232C is 15 m. The RS-232C standard, however, does not
cover baud rates above 19.2 Kbps. Refer to the manual for the device connected to confirm
support.
2
The total cable length for RS-422A/485 systems, including branch cables, is 1,200 m max. The
total cable length for RS-422A/485 systems, including branch cables, is 500 m max. when NT-
AL001 Link Adapters are used. The baud rate and the communications distance sometimes
depend on the remote device. Confirm the baud rates and communications distance sup-
ported by connected devices.
3
Here, the maximum cable length is limited to 2 m when an NT-Link Adapter is connected.
4
Branch lines must be a maximum of 10 m long.
Port
Config-
uration
Schematic diagram
RS-
422A/485
1:1
RS-
422A/485
1:N
RS-422A/485
RS-232C
interface
RS-422A/485
interface
NT-AL001
RS-232C
Resistance ON
5-V power
RS-422A/485
RS-422A/485
RS-422A/485
Resistance ON
B500-AL001-E
Resistance
ON
Resistance
ON
Resistance ON
NT-AL001
RS-232C
RS-232C
RS-232C
Resistance ON
5-V power
Resistance
ON
RS-422A/485
RS-232C
interface
RS-422A/485
interface
RS-422A/485
interface
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...