9 Troubleshooting and Maintenance
9-40
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event name
Command Error
Event code
54A8 0000 hex
Meaning
A command error occurred.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
After serial com-
munications start
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The constant in the expected receive
message that is set in the protocol
macro is different from the constant in
the message that was received.
Correct the expected receive mes-
sage that is set in the protocol macro
or the message that is sent by the
remote node so that the constant in
the message is the same.
Set the system so that the expected
receive messages that are set in the
protocol macros agree with the mes-
sages that are sent by the remote
nodes.
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Event name
Sequence Abort Completed
Event code
54A9 0000 hex
Meaning
The sequence was ended by an Abort setting for the next processing or error processing.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
At protocol macro
execution
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
The protocol macro data is not set
correctly.
The baud rate, frame format, or other
system setting does not agree with
the remote node.
Check if the protocol data and system
settings are set correctly with a trans-
mission line trace from the CX-Proto-
col.
Correctly set the protocol macro data.
Make sure that the baud rate, frame
format, and other system settings are
the same as for the remote nodes.
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...