9 Troubleshooting and Maintenance
9-12
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
The serial commu-
nications mode is
set to No-protocol
Mode.
---
With Unit: The
SerialRcv or
SerialRcvNo-
Clear instruc-
tion was
executed, but
data was not
received.
The Error output variable from the
SerialRcv or SerialRcvNoClear
instruction is TRUE.
•
This instruction
was executed
when the Serial
Communications
Mode was not No-
protocol Mode.
•
_Port_isAvailable
is set to FALSE.
•
The value of
Port.UnitNo or
Port.PhysicPortNo
is out of the valid
range.
•
The Serial Com-
munications Unit is
not mounted at the
specified Unit
number.
•
The value of Store-
Size is out of valid
range.
•
The value of Store-
Size exceeds the
size in DstDat[].
•
This instruction
was executed
while the unit was
restarting.
•
Review the set-
tings in the Serial-
Rcv or
SerialRcvNoClear
instruction.
•
Review the pro-
gram for instances
where the causes
specified on the
left might occur.
Command end code:
2201 hex (not possi-
ble during execu-
tion) was returned.
If the SerialRcv or
SerialRcvNoClear
instruction was exe-
cuted, the operation
is disabled because
the port is busy
receiving data.
Insert an AND in the
input condition for a
Network Communi-
cations Instruction
Enabled Flag
(_Port_isAvailable).
Command end code:
2202 hex (not possi-
ble while stopped)
was returned. Exe-
cution is not possible
while the protocol is
switched.
Insert an AND in the
input condition for an
N.C. of the Serial
Communications
Unit's Port 1/2 Set-
tings Changing Flag
(_CJB_SCU**P1(orP
2)ChgSta: Unit num-
ber **).
Error conditions
Confirmation of device
variable for CJ-series Unit, etc.
Cause
Remedy
Serial
communications
mode
Indicator
display
Status and
other
conditions
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...