Appendices
A-10
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
m = 100
×
unit number (word)
* Names used in CJ-Series
CJ-series I/O memory Address
NJ-series device variable for CJ-series Unit
Word No.
Bit No.
Variable name
Meaning
Port 1
Port 2
Port 1
Port 2
m+4
m+14
15 to 08
*_P1_NopStartCodeCf
g
*_P2_NopStartCodeCf
g
No-protocol Start Code
07 to 00
*_P1_NopEndCodeCf
g
*_P2_NopEndCodeCf
g
No-protocol End Code
m+5
m+15
15 to 00
*_P1_NopCfg
*_P2_NopCfg
No-protocol Settings
15 to 13
---
---
Reserved
12
*_P1_NopStartCodeY
NCfg
*_P2_NopStartCodeY
NCfg
No-protocol Start Code Inclusion
Setting
11 to 10
---
---
Reserved
09
*_P1_NopCRLFCfg
*_P2_NopCRLFCfg
No-protocol CR+LF Specification
Setting
08
*_P1_NopEndCodeYN
Cfg
*_P2_NopEndCodeYN
Cfg
No-Protocol End Code Inclusion Set-
ting
07 to 00
*_P1_NopRcvDatSzCf
g
*_P2_NopRcvDatSzCf
g
Number of Received Data Bytes in
No-protocol Mode
m+6
m+16
15 to 08
*_P1_MbsSlavAdrCfg
*_P2_MbsSlavAdrCfg
Modbus-RTU Slave Address
07 to 03
---
---
Reserved
02 to 00
*_P1_NtlMaxUnitNoCf
g
*_P2_NtlMaxUnitNoCf
g
1:N NT Links Maximum Unit Number
m+7
m+17
15 to 00
*_P1_PmrSgwTimeout
Cfg
*_P2_PmrSgwTimeout
Cfg
Serial Gateway Timeout Monitoring
Time Setting
15 to 08
*_P1_PmrSgwRespTi
meoutCfg
*_P2_PmrSgwRespTi
meoutCfg
Serial Gateway Response Timeout
Monitoring Time
07 to 00
*_P1_PmrSgwSendTi
meoutCfg
*_P2_PmrSgwSendTi
meoutCfg
Serial Gateway Send Start Timeout
Monitoring Time
m+8
m+18
15 to 00
*_P1_PmrTransCfg
*_P2_PmrTransCfg
Protocol macro Transmission Set-
tings
15
*_P1_PmrTransTypCfg
*_P2_PmrTransTypCfg
Protocol macro Transmission method
14 to 04
---
---
Reserved
03
*_P1_PmrRBufClrCfg
*_P2_PmrRBufClrCfg
Clearing/Holding the Contents of the
Reception Buffer in Full-duplex Mode
02
*_P1_PmrLkChAccess
Cfg
*_P2_PmrLkChAccess
Cfg
Link Word Specification Data
Exchange Method (Link Word Speci-
fication Data Exchange Method Tim-
ing (*))
01 to 00
---
---
Reserved
m+9
m+19
15 to 00
*_P1_PmrMaxDatSzC
fg
*_P2_PmrMaxDatSzC
fg
Maximum Number of Bytes in Proto-
col Macro Send/Receive Data
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...