5 Serial Gateway
5-24
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
z
Sending Messages Using SendCmd Instructions in CPU Unit's User Program
(The Unit converts the messages to CompoWay/F protocol)
Note 1
The header contains the following information.
•
Remote destination network address (DNA): Network address to specify actual remote
Pocasset 0 (local network).
•
Remote destination node address (DA1): Node address to specify actual remote Pocas-
set 0 (communications within local PLC).
•
Remote destination unit address (DA2):
Unit address of serial communications port. An appropriate value is calculated and set
as follows:
When port 1 is used: Unit address = BYTE#16#80 + BYTE#16#04
×
Unit number (hexa-
decimal)
When port 2 is used: Unit address = BYTE#16#81 + BYTE#16#04
×
Unit number (hexa-
decimal)
2
The contents of the CompoWay/F command enclosed in the message that is sent is as fol-
lows:
Node suba SID + command text (ASCII must be used.)
STX, ETX+BCC are not required when sending commands. They are added automatically
for serial communications.
System Configuration
CPU Bus-to-Serial
Details
From the CPU Unit, it is possible
to access OMRON components
that are connected to the Serial
Communications Unit via a
serial network (CompoWay/F).
2803
Header
FINS message
RS-485 (CompoWay/F)
CPU Unit
Serial Communications Unit
SendCmd
Protocol
conversion
CompoWay/F
command
CompoWay/F
command
CompoWay/F-compatible
OMRON component
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...