4-25
4 Using Protocol Macros
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
4-2 De
vic
e
V
ariab
les
fo
r CJ
-series Un
it and
Sys
tem-defined
V
ariables
(Pr
o
toco
l Macr
o Mo
de)
4
4-2-5 D
e
vice V
ar
iab
les f
or CJ-ser
ies U
nit f
o
r Status
*_P1_ParityBitSta
*_P2_ParityBitSta
BOOL
R
Parity
(Even/Odd)
FALSE: Even
TRUE: Odd
*_P1_HwSetSta
*_P2_HwSetSta
WORD
R
Hardware
Settings
Bit 15: RS-422/485 setting
status
Bit 14: RS-232C setting
Bit 13: Terminating resis-
tance setting status
Bit 01: System Setup error
Bit 00: Port operating sta-
tus
*_P1_Ser485Sta
*_P2_Ser485Sta
BOOL
R
RS-422/485
Setting Status
Port types of each port
*_P
@
_Ser485Sta/
*_P
@
_Ser232Sta:
00: No port
01: RS232C
10: RS422A/485
11: This status does not
exist.
*_P1_Ser232Sta
*_P2_Ser232Sta
BOOL
R
RS-232C Set-
ting Status
*_P1_TermSta
*_P2_TermSta
BOOL
R
Terminating
Resistance
Setting Status
TRUE: Terminating resis-
tance ON
FALSE: Terminating resis-
tance OFF
*_P1_SysSetupErr
*_P2_SysSetupErr
BOOL
R
System Setup
error
TRUE: System Setup
error
FALSE: System Setup
normal
*_P1_OperatingSta
*_P2_OperatingSta
BOOL
R
Port Operating
Status
TRUE: Port operating
FALSE: Port stopped
*_P1_TransCtlSta
*_P2_TransCtlSta
WORD
R
Communica-
tions Status
Bit 10: Remote Unit busy
Bit 08: Local Unit busy
Bit 07: DTR (ER) signal
Bit 06: DSR (DR) signal
Bit 04: CTS (CS) signal
Bit 03: RTS (RS) signal
*_P1_RmtBusySta
*_P2_RmtBusySta
BOOL
R
Remote Unit
Busy
TRUE: Remote Unit busy
(Flow control)
FALSE: Remote Unit
ready to receive
*_P1_LclBusySta
*_P2_LclBusySta
BOOL
R
Local Unit
Busy
TRUE: Local Unit busy
(Flow control)
FALSE: Local Unit ready
to receive
*_P1_SigERSta
*_P2_SigERSta
BOOL
R
ER signal
TRUE: High
FALSE: Low
*_P1_SigDRSta
*_P2_SigDRSta
BOOL
R
DR signal
TRUE: High
FALSE: Low
*_P1_SigCSSta
*_P2_SigCSSta
BOOL
R
CS signal
TRUE: High
FALSE: Low
*_P1_SigRSSta
*_P2_SigRSSta
BOOL
R
RS signal
TRUE: High
FALSE: Low
Device variable for CJ-series Unit
Type
R/W
Name
Function
Port 1
Port 2
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...