9 Troubleshooting and Maintenance
9-44
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
Event name
Timeout Error
Event code
64A4 0000 hex
Meaning
A timeout error occurred.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
After serial com-
munications start
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
In Protocol Macro Mode (the SD
@
indicator does not flash at all): The
Serial Communications Unit received
a command, but the step transition of
the protocol macro communications
sequence is suspended for one of the
following reasons.
•
The next step is a RECEIVE com-
mand.
•
A WAIT command is presently in
execution.
Review the communications
sequence. Or, program retry process-
ing in the device that sent the com-
mand when response code 0204 hex
is received. If necessary, adjust the
Serial Gateway Send Start Timeout
Monitoring Time in the
*_P1_PmrSgwSendTimeoutCfg or
*_P2_PmrSgwSendTimeoutCfg
device variable.
Perform countermeasures in
advance.
In Serial Gateway Mode or Protocol
Macro Mode (the SD
@
indicator
flashes, but the RD
@
does not flash):
•
There is no remote device to
receive the command after conver-
sion at the specified destination
address.
•
The sent command frame is illegal.
•
The settings for the communica-
tions conditions and baud rate of
the serial communications path do
not match the remote device.
•
The communications cable wiring is
faulty or incorrect, the terminating
resistance settings of the RS-
424A/485 port are incorrect, or the
adapter wiring or terminating resis-
tance settings for the NT-AL001 are
incorrect.
•
The protocol of the sent command
was unable to be interpreted by the
remote device.
•
Remote device hardware failure
•
Check the device at the specified
destination address.
•
Review the command frame to con-
vert.
•
Review the system settings and the
settings of the remote device.
•
Check the communications cable
connections. Turn ON the terminat-
ing resistance (with the terminating
resistance ON/OFF switch) at both
ends (at the remote device or at the
Unit).
•
Check the command specifications
of the remote device and conver-
sion source.
•
Replace the remote device.
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...