9 Troubleshooting and Maintenance
9-26
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-4-2
Error Contents and Details
Error code
Error contents
Details
Stored in
EEPROM
First byte
Second byte
0001 Hex
CPU Unit watchdog timer
error
Always 00 Hex
Always 00 Hex
Yes
0002 Hex
CPU Unit service monitor-
ing error
Monitoring time (Unit: 1 ms)
Yes
0006 Hex
Other CPU Unit errors
Bit 11: The unit number is not included in the Unit Configura-
tion in the CPU Unit.
Other bits not used.
Yes
000F Hex
CPU Unit initial processing
error
Always 00 Hex
Always 00 Hex
Yes
0011 Hex
CPU Unit initial processing
error
Not fixed
Not fixed
Yes
0012 Hex
CPU Unit memory error
01 Hex: Read error
02 Hex: Write error
03 Hex: Routing tables
05 Hex: System Settings
Data for the Unit
No
0108 Hex
Send not possible because
Unit is not detected
Event Send/Receive Errors
Commands:
Send source network address < 80
Bit 15:
OFF
Bits 08 to 14:
Send source network address
Bits 00 to 07:
Send source node address
Send source network address
≥
80
Bit 15:
OFF
Bits 08 to 14:
00
Bits 00 to 07:
Send source network address
Responses:
Send destination network address < 80
Bit 15:
ON
Bits 08 to 14:
Send destination network address
Bits 00 to 07:
Send destination node address
Send destination network address
≥
80
Bit 15:
ON
Bits 08 to 14:
00
Bits 00 to 07:
Send destination network address
No
010B Hex
Send not possible due to
CPU Unit error
No
010D Hex
Send not possible due to
remote address setting
error
No
010E Hex
Send not possible because
routing tables are not set
properly
No
0112 Hex
Send not possible due to
header setting error
No
0117 Hex
Internal reception buffer full
No
0118 Hex
Illegal packet discarded
No
011B Hex
Parity error
01 Hex: Port 1
02 Hex: Port 2
Always 00 Hex
No
011C Hex
Framing error
No
011D Hex
Overrun error
No
011E Hex
FCS check error
No
021A Hex
Setting table logic error
Always 00 Hex
03 Hex: Routing tables
05 Hex: System Settings
Data for the Unit
No
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...