9-15
9 Troubleshooting and Maintenance
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-3 T
rou
b
lesho
o
ting
9
9-3-2 No-protocol Mode
The serial commu-
nications mode is
set to No-protocol
Mode.
---
The SerialSend
instruction was
executed, but
sending was
not executed.
The output variable Error of the
SerialSend instruction is TRUE.
•
This instruction
was executed
when the Serial
Communica-
tions Mode was
not No-protocol
Mode.
•
_Port_isAvailable
is set to FALSE.
•
The value of
Port.UnitNo or
Port.Phys-
icPortNo is out of
the valid range.
•
The Serial Com-
munications Unit
is not mounted
at the specified
Unit number.
•
The value of
SendSize is out
of valid range.
•
The value of
SendSize
exceeds the size
in SrcDat[].
•
This instruction
was executed
while the unit
was restarting.
•
Review the setting
contents for the
SerialSend instruc-
tion.
•
Review the pro-
gram for instances
where the causes
specified on the left
might occur.
Command end
code: 2201 hex
(not possible dur-
ing execution) was
returned.
If the SerialSend
instruction was
executed, the
operation is dis-
abled because the
port was busy
while sending.
Insert an AND in the
input condition for an
N.C. of the Seri-
alSend Executing
Flag
(*_P1(orP2)_NopSeri
alSendExecSta).
Command end
code: 2202 hex
(not possible while
stopped) was
returned. Execu-
tion is not possible
while the protocol is
switched by using
the SerialSetUp
instruction.
Insert an AND in the
input condition for an
N.C. of the Serial
Communications
Unit's Port Settings
Change Bit
(_CJB_SCU**P1(orP
2)ChgSta: Unit num-
ber **).
---
---
A hardware error
occurred in the
transmission cir-
cuit.
Conduct a loopback
test in serial commu-
nications mode to
check the transmis-
sion lines. If an error
occurs during the
test, replace the Unit.
Error conditions
Confirmation of device variable
for CJ-series Unit, etc.
Cause
Remedy
Serial
communications
mode
Indicator
display
Status
and other
conditions
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...