9-21
9 Troubleshooting and Maintenance
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-3 T
rou
b
lesho
o
ting
9
9-3-3 Proto
c
ol Macros
The following table shows the measures to correct the errors indicated in bits 00 to 03 (Error code) of
*_P1(or P2)_PmrSta.
Note
For details on the protocol macros, refer to the CX-Protocol Ver.1.9 OPERATION MANUAL (Cat.
No. W344).
Remedy for Each Protocol Macro Error Code
Error
code
Indicator
Error details
Cause
Remedy
0 Hex
No display
Normal
---
---
1 Hex
No display
Reserved
---
---
2 Hex
No display
Sequence num-
ber error
The communications sequence
number specified in the Exec
PMCR instruction's SeqNo oper-
and which is not registered.
Correct the communications sequence num-
ber.
Use CX-Protocol to register the specified
communications sequence number.
3 Hex
ERC:
Flashing
ERR/ALM:
Flashing
Data read/write
range error
The data range of the specified
area is exceeded when data is
written to or read from the
CPU Unit.
For operand specification:
Check the in-out variable settings for the
ExecPMCR instruction.
For direct specification of link words:
Use CX-Protocol to check the specified
range.
4 Hex
ERC:
Flashing
ERR/ ALM:
Flashing
Protocol data syn-
tax error
There is a code that cannot be
executed during protocol execu-
tion.
Check the following items and correct the
problem.
•
Check whether the total specified number
of link words in the area (O1, O2, I1, I2)
exceeds 500 words.
•
The same area with link word specification
is used by both ports 1 and 2.
•
A write instruction with constant specifica-
tion is specified.
•
An interrupt notification is specified at the
Unit.
•
There are more than 30 write attributes set
for one message.
•
The length of a send/receive message is
set to 0 bytes.
•
The length of a send/receive message is
longer than the maximum send/receive
message bytes setting.
•
No messages are registered for matrix
reception.
•
Both RTS/CTS flow control and Xon/Xoff
flow control are set for the same transmis-
sion line.
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...