R-121
A Standard System Protocol
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
R-6 Ha
y
es Mod
e
m A
T
Com
m
and
Pr
otoc
o
l
Re
f
R
-6-4
Modem Settings
The following command is set in the words specified by the 3rd operand of PMCR(260).
ATE0V0X4\V2\N3%C0*C0\X1&M0S26=10
Additional Information
Turn ON pin 4 of DIP switches SW3 for this Modem (ER signal always ON).
MD144FB5V (OMRON, No longer manufactured.)
The following command is set in the words specified by the second operand of PMCR(260).
ATE0V0X4\V2\N3%C0*C0\Q0&M0&D0%B9600S26=10
ME1414B
III
/ME2814B
II
(OMRON)
The following command is set in the words specified by the second operand of PMCR(260).
AT\J1B8E0V0S0=1X4\V2\N3&M0%C0&D0&E0\X1S26=10
Additional Information
Turn ON DIP switch SW3 in the rear of the Modem.
To dial a telephone numbers for the OMRON ME1414B
III
/ME2814B
II
Modems using sequences No.
561, 571, 581, set the dialling command and telephone number in the words specified by the 3rd oper-
and of PMCR(260). However, for other Modems, make the following settings for the sequence No. 553,
Data Send/Receive (general purpose sequence).
This is an example of telephone number settings for the above mentioned 4 OMRON Modems.
Dial (Sequences No. 561 (Hex 0231), No. 571 (Hex 023B), and
No. 581 (Hex 0245))
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
A T E 0 V 0 X 4 \ V 2 \ N 3 % C 0 * C 0 \ X 1 & M 0 S 2 6 = 1 0
0020
0012
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
A T E 0 V 0 X 4 \ V 2 \ N 3 % C 0 * C 0 \ Q 0 & M 0 & D 0 % B 9
0029
0017
6 0 0 S 2 6 = 1 0
Character string length of modem initialization command (bytes)
Code length of PMCR(260) when it is used (words)
A T \ J 1 B 8 E 0 V 0 S 0 = 1 X 4 \ V 2 \ N 3 & M 0 % C 0 & D 0
002C
0018
& E 0 \ X 1 S 2 6 = 1 0
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...