9-13
9 Troubleshooting and Maintenance
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-3 T
rou
b
lesho
o
ting
9
9-3-2 No-protocol Mode
The serial commu-
nications mode is
set to No-protocol
Mode.
---
---
Overrun Error
*_P1(orP2)_OverRunErr is TRUE.
The reception buffer
received more than
259 bytes of data
before the SerialRcv
or SerialRcvNo-
Clear instruction was
executed.
Cycle the power or
restart the Unit and
clear the reception
buffer.
The Overrun Error
Flag is turned to
FALSE when the
reception buffer is
cleared.
---
The Reception Overflow Flag is
ON.
*_P1(orP2)_NopRcvOvfSta is
TRUE.
After reception was
completed (after the
Reception Com-
pleted Flag turned
ON), further data
was received (1 byte
or more).
After data reception
is completed (i.e.,
after the Reception
Completed Flag
changes to TRUE),
execute the Serial-
Rcv or SerialRcvNo-
Clear instruction
again.
---
The Reception Completed Flag is
OFF.
*_P1(orP2)_NopRcvCompleteSta
is FALSE.
Reception for the
SerialRcv or Serial-
RcvNoClear instruc-
tion was not
completed. One of
the following is the
cause.
---
The start
code/end code
setting is incor-
rect.
Revise the settings
for the Start
Code/End Code in
*_P1(orP2)_NopStar
tCodeCfg (No-proto-
col Start Code),
*_P1(orP2)_NopEnd
CodeCfg (No-proto-
col End Code).
No data was
received.
The specified
number of data
bytes was not
received.
Revise the specified
number of receive
data bytes in
*_P1(orP2)_NopRcv
DatSzCfg (Number
of Receive Data
Bytes in No-protocol
Mode).
Overrun error
(The reception
buffer received
more than 259
bytes of data
before the Serial-
Rcv or Serial-
RcvNoClear
instruction was
executed.)
Cycle the power or
restart the Unit to
clear the reception
buffer.
The Overrun Error
Flag is turned to
FALSE when the
reception buffer is
cleared.
---
---
A hardware error
occurred in the
reception circuit of
the Unit.
Conduct a loopback
test in serial commu-
nications mode to
check the transmis-
sion lines. If an error
occurs during the
test, replace the Unit.
Error conditions
Confirmation of device
variable for CJ-series Unit, etc.
Cause
Remedy
Serial
communications
mode
Indicator
display
Status and
other
conditions
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...