7-21
7 Using Modbus-RTU Slave Mode
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
7-3 Co
mm
and
and
Resp
onse
Detail
s
7
7-3
-2 Comma
nd and Response Det
ails
z
Response
z
Writing 10 Bits Starting from CIO 0001.04
(xxxx xx11 1100 1101)
Note
The subscript numbers in the shaded boxes indicate the TRUE/FALSE (1/0) status of the cor-
responding bits. Other bits in the same word are set to FALSE.
z
Function
Writes multiple words in the DM or EM Area of the memory used for CJ-series Unit.
z
Command
* N = Number of write bytes
Length
Data
Function Code
1 byte
0F hex
Starting Address
2 bytes
0000 to FFFF hex
Quantity of Output
2 bytes
0001 to 07B0 hex
Request
Response
Data
Data
Function Code
0F hex
Function Code
0F hex
Starting Address (H)
00 hex
Starting Address (H)
00 hex
Starting Address (L)
14 hex
Starting Address (L)
13 hex
Quantity of Output (H)
00 hex
Quantity of Output (H)
00 hex
Quantity of Output (L)
0A hex
Quantity of Output (L)
0A hex
Byte Count
02 hex
Output Value (H)
3A hex
Output Value (L)
01 hex
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CIO 0
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
CIO 1
31
0
30
0
29
0
28
1
27
0
26
0
25
1
24
1
23
1
22
0
21
1
20
0
19
0
18
0
17
0
16
0
Write Multiple Registers
Length
Data
Function Code
1 byte
10 hex
Starting Address
2 bytes
0000 to 7FFF hex
Quantity of Regis-
ters
2 bytes
0001 to 007B hex
Byte Count
1 byte
2
×
N (*)
Registers Value
N
×
2 bytes
value
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...