9-43
9 Troubleshooting and Maintenance
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
9-5 Even
t L
ogs
9
9-5-3 Error De
scr
iptio
ns
Event name
Tr (Receive Wait Monitoring Time) Exceeded
Event code
64A2 0000 hex
Meaning
The receive waiting time exceeded the Receive Wait Monitoring Time.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
After serial com-
munications start
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
Noise
Implement noise countermeasures.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
The monitoring time is shorter than
the actual completion time.
Adjust the monitoring time to match
the actual completion time.
Adjust the monitoring time to match
the actual completion time.
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Event name
FCS Check Error
Event code
64A3 0000 hex
Meaning
One of the following errors occurred in the converted protocol at the serial gateway.
•
When converting to CompoWay/F command: BCC error
•
When converting to Modbus-RTU command: CRC error
•
When converting to Modbus-ASCII command: CRC error
•
When converting to Host Link FINS command: FCS error
Protocol Macros
•
The check code attached to the received message does not match the check code that was calculated from the
received message.
Source
PLC Function Module
Source details
CJ-series Unit
Detection
timing
After serial com-
munications start
Error attributes
Level
Observation
Recovery
---
Log category
System
Effects
User program
Continues.
Operation
Not affected.
System-defined
variables
Variable
Data type
Name
None
---
---
Cause and
correction
Assumed cause
Correction
Prevention
Noise
Implement noise countermeasures.
Increase the setting for the number of
resends in the device that sent the
command.
If required, perform retry processing
for communications.
Use the Unit away from sources of
noise. Implement noise countermea-
sures.
Increase the setting for the number of
resends in the device that sends the
command.
If required, perform retry processing
for communications.
There was a mistake in the CRC code
that was attached to the command
frame.
Attach the correct CRC code.
Attach the correct CRC code.
Attached
information
Attached information 1: Port number where error was detected
Precautions/
Remarks
None
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...