7 Using Modbus-RTU Slave Mode
7-10
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
*_P1_StopBitSta
*_P2_StopBitSta
BOOL
R
Stop Bits (2
bits/1 bit)
FALSE: 2 bits
TRUE: 1 bit
*_P1_ParityYNSta
*_P2_ParityYNSta
BOOL
R
Parity
(Yes/No)
FALSE: Yes
TRUE: No
*_P1_ParityBitSta
*_P2_ParityBitSta
BOOL
R
Parity
(Even/Odd)
FALSE: Even
TRUE: Odd
*_P1_HwSetSta
*_P2_HwSetSta
WORD
R
Hardware
Settings
Bit 15: RS-422/485 setting status
Bit 14: RS-232C setting status
Bit 13: Terminating resistance set-
ting status
Bit 01: System Setup error
Bit 0: Port operating status
*_P1_Ser485Sta
*_P2_Ser485Sta
BOOL
R
RS-422/485
Setting Sta-
tus
Port types of each port
*_P_Ser485Sta/*_P_Ser232Sta:
00: No port
01: RS232C
10: RS422A/485
11: This status does not exist.
*_P1_Ser232Sta
*_P2_Ser232Sta
BOOL
R
RS-232C
Setting Sta-
tus
*_P1_TermSta
*_P2_TermSta
BOOL
R
Terminating
Resistance
Setting Sta-
tus
TRUE: Terminating resistance ON
FALSE: Terminating resistance
OFF
*_P1_SysSetupErr
*_P2_SysSetupErr
BOOL
R
System
Setup error
TRUE: System Setup error
FALSE: System Setup normal
*_P1_OperatingSta
*_P2_OperatingSta
BOOL
R
Port Operat-
ing Status
TRUE: Port operating
FALSE: Port stopped
*_P1_TransCtlSta
*_P2_TransCtlSta
WORD
R
Communica-
tions Status
Bit 10: Remote Unit busy (*2)
Bit 08: Local Unit busy (*3)
Bit 07: DTR (ER) signal
Bit 06: DSR (DR) signal
Bit 04: CTS (CS) signal
Bit 03: RTS (RS) signal
*_P1_RmtBusySta
*_P2_RmtBusySta
BOOL
R
Remote Unit
Busy (*2)
TRUE: Remote Unit busy (Flow
control)
FALSE: Remote Unit ready to
receive
*_P1_LclBusySta
*_P2_LclBusySta
BOOL
R
Local Unit
Busy (*3)
TRUE: Local Unit busy (Flow con-
trol)
FALSE: Local Unit ready to receive
*_P1_SigERSta
*_P2_SigERSta
BOOL
R
ER signal
TRUE: High
FALSE: Low
*_P1_SigDRSta
*_P2_SigDRSta
BOOL
R
DR signal
TRUE: High
FALSE: Low
*_P1_SigCSSta
*_P2_SigCSSta
BOOL
R
CS signal
TRUE: High
FALSE: Low
*_P1_SigRSSta
*_P2_SigRSSta
BOOL
Rl
RS signal
TRUE: High
FALSE: Low
Device variable for CJ-series Unit
Type
R/W
Name
Function
Port 1
Port 2
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...