4 Using Protocol Macros
4-22
CJ-series Serial Communications Units Operation Manual for NJ-series CPU Unit(W494)
The device variables can be used to execute various commands for the Serial Communications Unit.
z
List of Areas
4-2-4
Devices Variable for CJ-series Unit for Software Switches
Device variable for CJ-series Unit
Type
R/W
Name
Function
Port 1
Port 2
*_P1_SoftSw
*_P2_SoftSw
BYTE
RW
Soft Switches
Bit 04: Serial Gateway
Prohibit Switch
Bit 03: Abort Switch
Bit 02: One-shot Trace
Switch
Bit 01: Continuous Trace
Switch
Bit 00: Wait Release
Switch
*_P1_SgwDsblCmd
*_P2_SgwDsblCmd
BOOL
RW
Serial Gateway
Prohibit Switch
(Protocol Mac-
ros)
TRUE
→
FALSE: Not pro-
hibited
FALSE
→
TRUE: Prohib-
ited
*_P1_PmrAbtCmd
*_P2_PmrAbtCmd
BOOL
RW
Abort Switch
(Protocol Mac-
ros)
TRUE: Abort
FALSE: Aborted
*_P1_Pmr1ShotTrace
Cmd
*_P2_Pmr1ShotTrace
Cmd
BOOL
RW
One-shot Trace
Switch (Proto-
col Macros)
(*1)
TRUE: Start
FALSE: Stop
*_P1_PmrContTraceC
md
*_P2_PmrContTraceC
md
BOOL
RW
Continuous
Trace Switch
(Protocol Mac-
ros) (*1)
TRUE: Start
FALSE: Stop
*_P1_PmrWaitRlsCmd
*_P2_PmrWaitRlsCmd
BOOL
RW
Wait Release
Switch (Proto-
col Macros)
TRUE: Release Wait
FALSE: Wait released
Содержание CJ1W-SCU22
Страница 192: ...4 Using Protocol Macros 4 56 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 250: ...6 No protocol Mode 6 22 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 460: ...A Standard System Protocol R 126 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494...
Страница 473: ...Index 1 CJ series Serial Communications Units Operation Manual for NJ series CPU Unit W494 I Index...