6 Wiring of the Device
Rev. 09/2019
47
Wiring MIC6 ignition controller and DetCon detonation control system
The following diagram shows an example of the wiring of a MIC6 ignition
controller with a DetCon detonation control system in cases where the
analog current signal (4-20 mA) at the output
I out
is to be used for the
ignition timing adjustment.
MIC6-
ignition
controller
DetCon
detonation
control system
Furthermore, the limits of the analog current input will need to be set at
4 mA to 20 mA and the auxiliary supply voltage of the analog inputs to 24 V
in the MICT. Refer to the section
Timing – Analog Inputs
The timing is transmitted by MIC6 via the auxiliary synchronization output
(ASO) to the DetCon, and will need to be wired and configured accordingly.
Refer to the section
Output Wiring – Binary Outputs (Go/NoGo, GPO, ASO)
on page 48.
General purpose input GPI
The general purpose input GPI can be assigned various functions via the
configuration. Refer to the section
Inputs/Outputs – Inputs