8 Settings via the MICT
152
Rev. 09/2019
Adjust the sensitivity of the short-circuit monitoring
If a short-circuit is misdiagnosed at a sensitivity of 1.00, the sensitivity
must be set to 1.02.
If a short-circuit is not detected at a sensitivity of 1.00, the sensitivity must
be set to 0.98.
8.15
Cylinder Individual Offsets
Click on the symbol to open the window
Cylinder Individual Offsets
. This
window is only available to users with authorizations starting with access level
Service
.
The cylinder individual offset can be applied to the position of the timing point while the
controller is being operated. Offset via keys:
–
0.1 ADV/RET
in 0.1° increments to advance or retard
–
0.5 ADV/RET
in 0.5° increments to advance or retard
The adjustment option of this function is limited by the specified settings in the configuration.
Refer to the section
Timing – Schedule A/B – General
on page 104.