Runtime Adjustments – Secondary Short Calibration
The starting voltage and sensitivity for the secondary short-circuit detection can be adjusted.
Changes are implemented immediately and stored in the configuration provided in the device.
Secondary Short Enable Voltage [kV]
Set the necessary average ignition voltage required to activate the secondary short-circuit
monitoring:
–
The secondary short detection is always activated at a value of 0 kV.
–
The secondary short detection is always deactivated at a value of 65.535 kV.
Secondary Short Sensitivity
The permitted value range depends on the set ignition coil.
Set the sensitivity of the short-circuit detection e.g. as follows:
–
The sensitivity is high at a value of 0.98.
–
The sensitivity is low at a value of 1.02.