![Motortech MIC-Marine Скачать руководство пользователя страница 125](http://html1.mh-extra.com/html/motortech/mic-marine/mic-marine_operating-manual_1839332125.webp)
8 Settings via the MICT
Rev. 09/2019
125
Date and time of ignition controller
The date and time can be individually configured for each ignition controller
and saved in the device. The device does not adjust automatically for
daylight savings time. Hence, deviations may occur between the device
time and the time on the computer used to access the device.
Correspondingly, the times indicated for the states, messages, and in the
log reflect the time of the ignition controller. The current time of the ignition
controller is shown in the view
Runtime Data – Information
. You can adjust
the time of the ignition controller by entering the desired time in the menu
via
Device -> Set date and time
.
Status messages are displayed in black if they are current. If a status is reset, the status
message is displayed gray for 10 seconds before it is deleted from the list.
The following status messages can be displayed:
Status message
Description
Alarm shutdown caused by
alarm
number
.
The engine was shut down by an alarm, as the configured
limit was exceeded or not reached. You can view the alarm
number
in the configuration (see
Inputs/Outputs – Alarms
on page 108).
Analog current input failure
(current:
x mA
, failure threshold:
y mA
, failure reset threshold:
z mA
).
Failure threshold set for analog current input was
undershot (see
Timing – Analog Inputs
The following values were obtained: Current:
x mA
, failure
threshold:
y mA
, threshold for failure reset:
z mA
.
Analog voltage input failure
(voltage:
x V
, failure threshold:
y V
, failure reset threshold:
z V
).
Failure threshold set for analog voltage input was
undershot (see
Timing – Analog Inputs
The following values were obtained: Voltage:
x V
, failure
threshold:
y V
, threshold for failure reset:
z V.
Aux analog input supply voltage
failure (voltage:
u V
, desired
voltage:
v V
, failure threshold:
x V, failure reset threshold: y V).
Error in auxiliary supply voltage of analog inputs (see
Timing – Analog Inputs
on page 103). The following values
were obtained: Voltage:
u V
, expected voltage:
v V
, failure
threshold:
x V
, threshold for failure reset:
y V
Aux pickup supply voltage
failure (voltage:
u V
, desired
voltage:
v V
, failure threshold:
x V, failure reset threshold: y V).
Error in auxiliary supply voltage of pickup (see
Engine –
Pickups – General
on page 98). The following values were
obtained: Voltage:
u V
, expected voltage:
v V
, failure
threshold:
x V
, threshold for failure reset:
y V
Configuration data checksum
error. Using default
configuration.
The checksum of the configuration data is faulty. The
default configuration is used. This message may appear
during an upgrade/downgrade. Check your configuration
data and the MICT version being used. Then download the
configuration to the device once again.