Selection and protection of a motor
Parameter
6 - 222
6.12.3
Offline auto tuning
(Pr. 71, Pr. 80 to Pr. 84, Pr. 90 to Pr. 94, Pr. 96, Pr. 450, Pr. 453 to Pr. 463,
Pr. 684, Pr. 859, Pr. 860)
The motor performance can be maximized with offline auto tuning.
What is offline auto tuning?
●
When performing advanced magnetic flux vector control, real sensorless vector control or
vector control, the motor can be run with the optimum operating characteristics by automa-
ticaly measuring the motor constants (offline auto tuning) even when each motor constants
differs, other manufacturer's motor is used, or the wiring length is long.
Pr.
No.
Name
Initial
Value
Setting Range
Description
Parameters referred to
Refer to
Section
71
Applied motor
0
0 to 8/13 to 18/20/
23/24/30/33/34/40/
43/44/50/53/54
By selecting a standard motor or
constant-torque motor, thermal
characteristic and motor con-
stants of each motor are set.
7
8
9
71
80
81
95
156
178–189
190–196
800
Acceleration time
Deceleration time
Electronic ther-
mal O/L relay
Applied motor
Motor capacity
Number of motor
poles
Online auto tuning
selection
Stall prevention
operation selec-
tion
Input terminal
function selection
Output terminal
function selection
Control method
selection
80
Motor capacity
9999
01800
or
less
0.4 to
55kW
Applied motor capacity
02160
or
more
0 to
3600kW
9999
V/f control
81
Number of motor
poles
9999
2/4/6/8/10
Number of motor poles
12/14/16/18/20
X18 signal ON: V/f control
Set 10 + number
of motor poles.
9999
V/f control
82
Motor excitation
current
9999
01800
or
less
0 to 500A
Tuning data
(The value measured by offline
auto tuning is automatically set.)
02160
or
more
0 to 3600A
9999
Uses the Mitsubishi motor
(SF-JR, SF-HR, SF-JRCA,
SF-HRCA) constants.
83
Motor rated voltage
400V
0 to 1000V
Rated motor voltage (V)
84
Rated motor
frequency
50Hz
10 to 120Hz
Rated motor frequency (Hz)
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless
Vector
Vector
Vector
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......