Useful functions
Parameter
6 - 532
6.25.4
Current average value monitor signal (Pr. 555 to Pr. 557)
The average value of the output current during constant speed operation and the maintenance
timer value are output as a pulse to the current average value monitor signal (Y93). The pulse
width output to the I/O module of the PLC or the like can be used as a guideline due to abrasion
of machines and elongation of belt and for aged deterioration of devices to know the mainte-
nance time.
The current average value monitor signal (Y93) is output as pulse for 20s as 1 cycle and repeat-
edly output during constant speed operation.
The above parameters allow its setting to be changed during operation in any operation mode
even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
I001264E
Fig. 6-267:
Monitoring the maintenance timer and current average value
Pr. No.
Name
Initial
Value
Setting
Range
Description
Parameters referred to
Refer to
Section
555
Current average time
1s
0.1–1.0s
Set the time taken to average
the current during start bit out-
put (1s).
190–196
503
57
Output terminal
function selection
Maintenance timer
Restart coasting
time
556
Data output mask time
0s
0.0–20.0s
Set the time for not obtaining
(mask) transient state data.
557
Current average value
monitor signal output
reference current
Rated
inverter
current
01800
or less
0–500A
Set the reference (100%) for
outputting the signal of the cur-
rent average value.
02160
or
more
0–3600A
Maintenance
time
Parts have
reached their life!
Input unit
Output unit
Inverter
PLC
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......