Frequency/torque setting by analog input (terminals 1, 2 and 4)
Parameter
6 - 396
Analog input display unit changing (Pr. 241)
You can change the analog input display unit (%/V/mA) for analog input bias/gain calibration.
Display unit of C17 (Pr. 919), C19 (Pr. 920), C39 (Pr. 932), C41 (Pr. 933) changes as follows
accrding to the terminal input specifications set in Pr. 73 and Pr. 267.
Note that the LEDs V or A also light up as an additional indicator when Pr. 241 is set to "1" and
the display is set to the settings for C16 to C19 resp. C38 to C41.
Analog Command (terminal 1, 4)
(according to Pr. 73, Pr. 267)
Pr. 241 = 0 (initial value)
Pr. 241 = 1
0 to 5V input
0 to 5V
→
0 to 100% (0.1%) is
displayed.
0 to 100%
→
0 to 5V (0.01V) is
displayed.
0 to 10V input
0 to 10V
→
0 to 100% (0.1%) is
displayed.
0 to 100%
→
0 to 10V (0.01V) is
displayed.
0/4 to 20mA input
0 to 20mA
→
0 to 100% (0.1%) is
displayed.
0 to 100%
→
0 to 20mA (0.01mA) is
displayed.
Tab. 6-113:
Units when displaying the set value