Parameter
Parameter overview
FR-A700 EC
6 - 17
Func-
tion
Parameter
Name
Incre-
ments
Initial
Value
Setting
Range
Description
Para-
meter
copy
Para-
meter
clear
All
para-
meter
clear
Refer
to
page
Re
la
te
d
parameters
✔
: enabled
—: disabled
Applied motor
71
Applied motor
1
0
0
Thermal characteristics of a stand-
ard motor
✔
✔
✔
1
Thermal characteristics of the Mit-
subishi constant-torque motor
2
Thermal characteristic of standard
motor
Adjustable 5 points V/f
20
Mitsubishi standard motor
(SF-JR 4P 1.5kW or less)
30
Thermal characteristics of the Mit-
subishi vector motor SF-V5RU
40
Thermal characteristic of Mitsubi-
shi high efficiency motor
(SF-HR)
50
Thermal characteristic of Mitsubi-
shi constant-torque motor
(SF-HRCA)
3
Standard
motor
Select "offline
auto tuning set-
ting"
13
Constant-
torque motor
23
Mitsubishi
standard
motor (SF-JR
4P 1.5kW or
less)
33
Mitsubishi
vector motor
(SF-V5RU/
SF-THY)
43
Mitsubishi
high efficiency
motor
(SF-HR)
53
Mitsubishi
constant-
torque motor
(SF-HRCA)
4
Standard
motor
Auto tuning data
can be read,
changed, and set.
14
Constant-
torque motor
24
Mitsubishi
standard
motor (SF-JR
4P 1.5kW or
less)
34
Mitsubishi
vector motor
(SF-V5RU/
SF-THY)
44
Mitsubishi
high efficiency
motor
(SF-HR)
54
Mitsubishi
constant-
torque motor
(SF-HRCA)
Tab. 6-1:
Parameter overview (17)
Содержание FR-A700 EC
Страница 2: ......
Страница 4: ......
Страница 24: ...Description of the Case Product Checking and Part Identification 1 4 ...
Страница 38: ...Enclosure design Installation 2 14 ...
Страница 774: ...Specifications FR A 740 01800 to 12120 Appendix A 4 ...
Страница 820: ...Parameter list with instruction codes Appendix A 50 ...
Страница 825: ......